This sets the integral time. It is valid only when SW203-1 is set to OFF (i.e., PID
control).
•
This value is reflected even when auto-tuning (AT) is executed.
SP Lower Limit (Display Level 1)
PV
SV
SP lower limit parameter symbol
SP lower limit of currently selected loop
(unit:
°
C or
°
F)
•
Settings can be made within the following range:
Sensor measuring range lower limit to (SP upper limit – 1 digit)
•
When powering up or starting, the lower limit of the measuring range for sen-
sors set by the rear-panel SW202 (sensor type) is set automatically. For exam-
ple, if SW202 is set to “2,” the thermocouple type is set to “–200.” However, the
SP lower limit will not be changed if the current SV lies inside the sensor mea-
suring range.
SP Upper Limit (Display Level 1)
PV
SV
SP upper limit parameter symbol
SP upper limit of currently selected loop
(unit:
°
C or
°
F)
•
Settings can be made within the following range:
(SP limit + 1 digit) to sensor measuring range upper limit
•
When powering up or starting, the upper limit of the measuring range for sen-
sors set by the rear-panel SW202 (sensor type) is set automatically. For exam-
ple, if SW202 is set to “2,” the thermocouple type is set to “1300.” However, the
SP upper limit will not be changed if the current SV lies inside the sensor mea-
suring range.
Dead Band (Display Level 1)
PV
SV
Dead band parameter symbol
Dead band of currently selected loop (unit:
°
C or
°
F)
•
This sets the cooling output dead band, and it is valid when SW203-1 (PID con-
trol) is OFF.
•
The relation between the dead band and the set temperature is as shown in the
illustration below.
Output volume
Heating output
Dead band
Cooling output
Temperature
Set value
100%
0%
Parameter Displays and Settings
Section 3-4
32 / 71