39
I/O
Data contents
Data item
Address
Bit
Word
Input
n+3
15 to 00
Loop 1 PV
Outputs the Loop 1 and Loop 2 PV (process value) as 4-digit
BCD data For platinum resistance thermometer data the least
n+4
15 to 00
Loop 2 PV
BCD data. For platinum resistance thermometer data, the least
significant digit is 0.1. The most significant digit is F for minus (–).
n+5
15 to 00
Loop 1 SP
Outputs the Loop 1 and Loop 2 SP (set point) as 4-digit BCD
data For platinum resistance thermometer data the least
n+6
15 to 00
Loop 2 SP
data. For platinum resistance thermometer data, the least
significant digit is 0.1. The most significant digit is F for minus (–).
n+7
15 to 12
Loop 1
executed
bank
number
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data.
11 to 08
Loop 2
executed
bank
number
07 to 02
---
Not used. Each bit is set to 0.
01
SW2-2
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: C200H PC
00
SW2-1
Outputs the ON/OFF status of SW2-1 (switching memory
contents).
0: Fixed
1: Normal
n+8 Loop 1
n+9 Loop 2
15
---
Not used. Set to 0.
Loop 1/2
status data
14
Sensor
error
Bit set to 1 if the sensor is not connected, a sensor
wire is broken, or the input data exceeds the
operational temperature range.
13
CT
overflow
Bit set to 1 when the detected heater current
exceeds 55.0 A.
12 to 09
---
Not used. Each bit is set to 0.
08
RUN
Bit set to 1 during operation.
07 and 06
---
Not used. Each bit is set to 0.
05
Cooling
control
output
Bit set to 1 when the control output (transistor or
voltage output) is ON.
04
Heating
control
output
03
AT
Bit set to 1 during auto-tuning (AT).
02
HB
Bit set to 1 if the detected heater current drops
below the set heater burnout current value. (HB:
heater burnout)
01
AL1
Bit set to 1 when the temperature enters the set
l
(R f
t
23)
00
AL2
alarm range (Refer to page 23).
Note If the setting direction of the Temperature Control Unit is set to the C200H PC
and the C200H is in program mode, all word data will be 0. Therefore, if the
C200H in program mode has been set to continuous control, the Temperature
Control Unit executes temperature control when the C200H stops operating,
judging that the SP has been changed to 0
°
C. To prevent this, set SW2-2 of the
Temperature Control Unit to OFF (i.e., the setting direction is set to the Data Set-
ting Console) before the C200H stops operating and reset SW2-2 after the
C200H restarts.
Memory Allocation
Section 4-1
42 / 71