SRT
j
-R
SRT
j
-R
38
Nomenclature
SRT2-ROC16
SRT2-ROF16
SRT1-ROC08
SRT1-ROF08
Mounting Holes
Output Terminals
I/O Power Supply Terminals
Connect 24-VDC power supply
Communications Power Supply Terminals
Connect 24-VDC power supply.
CompoBus/S Terminals
Connect the CompoBus/S communications cable.
Mounting Holes
DIP Switch
Used for node number setting and holding or
clearing outputs for communications error.
Note:
Always turn off the Unit before changing DIP switch settings.
Mounting Holes
Output Terminals
I/O Power Supply Terminals
Connect 24-VDC power supply
Communications Power Supply Terminals
Connect 24-VDC power supply.
CompoBus/S Terminals
Connect the CompoBus/S communications cable.
Mounting Holes
DIP Switch
Used for node number setting and holding or clearing outputs for communications error.
0 to 15
ERR
COMM
PWR
Output HOLD/CLEAR setting (Output model only)
Baud rate setting
Node address setting
Indicators
Indicator
Display
Color
Meaning
PWR
Lit
Green
The communications power supply is ON.
Not lit
The communications power supply is OFF.
COMM
Lit
Yellow
Normal communications
Not lit
A communications error has occurred or
the Unit is in standby status.
ERR
Lit
Red
A communications error has occurred.
Not lit
Normal communications or the Unit is in
standby status.
0 to 15
(see
note)
Lit
Yellow
The corresponding I/O signal is ON.
Not lit
The corresponding I/O signal is OFF.
Note:
The SRT1-RO
j
08 does not have indicators 8 to 15.