SRT
j
-R
SRT
j
-R
39
Output HOLD/CLEAR Mode
Mode
Pin 1
Setting
HOLD
ON
Output status is maintained when a communications error occurs.
CLEAR
OFF
Output status is cleared when a communications error occurs.
Note:
1. Pin 1 is factory-set to OFF.
2. This function is available to the Output Terminal only.
Node Number Settings
Node number
Pin 3
Pin 4
Pin 5
Pin 6
8
4
2
1
0
OFF
OFF
OFF
OFF
1
OFF
OFF
OFF
ON
2
OFF
OFF
ON
OFF
3
OFF
OFF
ON
ON
4
OFF
ON
OFF
OFF
5
OFF
ON
OFF
ON
6
OFF
ON
ON
OFF
7
OFF
ON
ON
ON
8
ON
OFF
OFF
OFF
9
ON
OFF
OFF
ON
10
ON
OFF
ON
OFF
11
ON
OFF
ON
ON
12
ON
ON
OFF
OFF
13
ON
ON
OFF
ON
14
ON
ON
ON
OFF
15
ON
ON
ON
ON
Note:
1. The node number is factory-set to 0.
2. For node number setting, refer to the
CompoBus/S Operation Manual (W266).
Содержание 3G8B3-SRM00
Страница 81: ...CompoBus S CompoBus S 90 Notes ...