3-1
3-1 Parameter Description of Each Function
3
Func
tions
3Functions
3-1 Parameter Description of Each Function
Binary Batch Input
The settings of frequency, torque limit and position can be selected using the rotary switch (CODE)
in a single data input.
The data bit configuration of the binary batch input is shown below.
Setting Example
When setting the frequency to 60 Hz with a resolution of 0.1 Hz (Rotary switch setting (CODE): 1)
1. Input the 16-bit binary value of 60 multiplied by 10 in terminals D15 to D0.
60
×
10 times = 600
→
0000001001011000 (binary)
2. When the data is entered, turn the strobe signal ON.
3. Turn the strobe signal OFF.
Precautions
For details on signal input timing, refer to "3-3 Data Input Timing"(Page 3-6).
DIP switch TYPE setting
1
2
OFF: BIN
OFF: PAC
D11
D10
D 9
D8
D7
D6
D5
D4
D3
D2
D1
D0
D15
D14
D13
D12
(MSB)
(LSB)
Set data
D11
D10
D 9
D8
D7
D6
D5
D4
D3
D2
D1
D0
16-bit data
1
1
1
1
0
0
0
0
D12
D13
D14
D15
0
0
0
0
0
0
0
0