OEL8000II
Owners Manual
3-25
3.2.2.12 DIAG
Submenu
The DIAG Submenu (see Figure 3-25a) is entered from Screen #5 of the MAIN
Menu. It allows you to enable/disable communications with remote sites and test
alarms for product and water levels
The second and third lines indicate whether CALLOUT is enabled or disabled. At
times, it may be necessary to prevent the system from calling out. This is because the
system will prevent access to its controls while a callout is in progress. To avoid
being locked out of the system while working on it, you can disable callout until
work is finished.
The second and third lines also identify the current setting for DIAG MODE
(diagnostic mode): DIAG-Prod (diagnostics for product), DIAG-Water (diagnostics
for water), and DIAG-OFF (diagnostic mode is off).
.---Shift Log
End Time
FR 02/02/07 18:00:00
Start Time
TH 02/01/07 12:00:00
Tank1, DIESEL
End Product Level:
43.56(In)
Start Product Level:
43.60(In)
End Product Vol.:
2942.97(In)
Start Product Vol.:
2945.66(In)
End T.C. Vol.:
2934.10(G)
Start T.C. Vol.:
2935.80(G)
End Water Level:
2.90(In)
Start Water Level:
2.85(In)
End Water Vol.:
195.68(In)
Start Water Vol.:
192.68(In)
End Temperature:
67.2(F)
Start Temperature:
68.0(F)
Delivery T.C. Vol.:
0.00(G)
Sold/Used Vol.:
2.70(G)
Figure 3-24b: Shift Log Data
TU 02/06/07
15:24:31
*STATUS:NORMAL
CALLOUT DIAG MODE
Enabled DIAG-OFF
E/D |P/W/O |
|EXIT
Fig. 3-25a: DIAG Submenu (Off)