30
Omniksol-3.68k-TL3
16A
16m
24m
Omniksol-4k-TL3
17.4A
15m
22m
Model
Rated current
Length of cable
6 mm
2
10 mm
2
Omniksol-5k-TL3
21.7A
18m
30m
Omniksol-6k-TL3
26A
15m
25m
1) Remove length y of
N, L
conductor 35mm (1.38’’)/
PE
conductor 40mm (1.57’’) sheath of AC
cable terminal, length x about 14mm (0.55’’) of the inner wrapper, then dress the conductor
terminals with ferrules or tin soldering.
2) Check that all parts of AC connector are present. Then slide hex nut onto the cable and
insert the cable end through clamp ring.
3) Insert the
stripped N, L and PE conductor terminal
to the appointed holes, use a cross
screwdriver to tighten it with tightening torque 1Nm.
4) Insert the connector to clamp ring with two click sound and then tighten the hex nut with
tightening torque 4Nm.