Static Pressure
EXTERNAL STATIC PRESSURE (in.w.c.)
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Model
24K
48K
36K
SP1
975
1076
675
853
/
502
/
/
/
1175
1250
965
1075
650
815
/
/
/
1415
1490
1250
1334
1028
1156
1756
1825
1592
1670
1450
1515
1270
1335
1062
1165
810
950
1405
1475
1230
1320
990
1125
1585
1648
1440
1515
1235
1354
1733
1815
1605
1663
1435
1528
1530
1611
1375
1462
1170
1276
1701
1774
1570
1642
1420
1504
1805
1868
1675
1736
1532
1604
1974
2024
1850
1919
1726
1795
750
1250
450
715
990
1235
925
1202
1330
1560
600
1120
240
570
875
1130
831
1081
1211
1466
880
1360
645
855
1125
1346
1025
1313
1433
1652
SP2
SP3
SP4
SP1
SP2
SP3
SP4
SP1
SP2
SP3
SP4
Page 11
Indoor Unit
Parts And
Major Functions
Static pressure selection ( For RG57 Remote Controller )
•
•
MODE
FAN
TEMP
SLEEP
L
SWING DIRECT
ED
TURBO
ON/OFF
TIMER
ON
TIMER
OFF
SHORT
CUT
The indoor unit should be operated within 10 minutes after
installation.
During the first 30 seconds after power on, press and hold the
following three buttons: MODE, FAN, and TIMERON; or the two
buttons of MODE and TIMERON for 5 seconds.
Step1
: Press “
△
” or “
▽
” to select the E9.
Step2
: Press “MODE” to set the air ow rate in the range of 1~4.
“1”~“4”
:
Air
ow increase progressively
Step3
: Press “MODE” to confirm
,
than Press “TIMERON ”to finish the air flow setting.
Step4
: Remove the remote controller battery, and then assemble the battery after the remote
controller screen is not displayed. The remote controller exits the modification mode.
After restarting, the machine will keep the setting's value.
AIR FLOW DATA (CFM)
NOTE:
1. This function is only suitable for debugging the machine with the RG57 remote controller. Changing
this only allows for professional installers to operate.
2. During the static pressure test, it is necessary to assemble the upper cover of the unit, otherwise
there may be deviations in the calculated data.
3. The remote controller is only allowed for static pressure debugging and static pressure test functions.
4. Illustrations in this manual are for explanatory purposes. The actual shape of your remote controller
may be slightly different.
5. Sp1 applies static pressure of 0~0.2 in w.c
Sp2 applies static pressure of 0.2~0.4 in w.c
Sp3 applies static pressure of 0.4~0.6 in w.c
Sp4 applies static pressure of 0.6~0.8 in w.c