OMEGA-VSHP.F-IOM-1907
www.omega-heatpump.com
36
Note: All airflow ratings are taken at lowest voltage rating of dual rating (ie. 208 volt).
Airflow ratings include resistance of dry coil, Return Air panel and clean MERV10 air filters.
Contact customer service for external static pressure requirements exceeding 0.5” w.g.
Model
Min.
SCFM
Rated
SCFM
Speed
External Static Pressure (in w.g.)
0
0.1
0.2
0.3
0.4
0.5
0.6
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
020
150
200
LOW
285
230
210
195
160
-
-
MED
320
270
250
225
200
160
-
HIGH
430
355
340
315
280
240
185
030
210
350
LOW
275
235
220
-
-
-
-
MED
310
275
250
230
-
-
-
HIGH
405
370
350
315
280
235
-
040
270
460
LOW
340
300
275
-
-
-
-
MED
410
370
350
338
315
-
-
HIGH
600
550
520
500
380
310
-
050
370
530
LOW
560
510
475
450
-
-
-
MED
645
585
550
505
460
415
-
HIGH
765
715
670
630
585
530
455
060
410
630
LOW
560
510
475
450
-
-
-
MED
645
585
550
505
460
415
-
HIGH
765
715
670
630
585
530
455
080
270
820
LOW
785
735
700
655
615
570
-
MED
855
790
750
710
670
615
-
HIGH
895
840
790
745
710
645
600
100
640
1010
LOW
895
855
790
745
670
-
-
MED
1045
970
925
855
785
710
-
HIGH
1155
1075
1010
935
845
775
670
120
740
1200
LOW
1155
1080
1015
950
875
790
-
MED
1170
1095
1025
970
890
800
-
HIGH
1225
1150
1080
1000
935
850
760
Table 17
PSC Fan Data