9.6.4
Process IPSO Definition
The IPSO process definition provides signal range, measured min/max values, IPSO object type information.
Offset
Name
Value
Description
0x08a8
Sensor Type
3317
Current (mA)
3316
Voltage (mv)
0x08aa
Precision
0-24mA
1 – display as xx.x
0-1000 mV
-1 – display as xxx0.0
0-2000 mV
-1 – display as xxx0.0
0x08ac Sensor Trigger
??
Write any value to force a reset of min/max
0x08b0 Min Measured
??
Minimum reading since the last reset
0x08b4 Max Measured
??
Maximum reading since the last reset
0x08b8
Min Range
Range
Minimum Maximum
0-24 mA
0
24 mA
0 – 1 Vdc
0
1000 mV
0 – 2 Vdc
0
2000 mV
0x08bc
Max Range
9.6.4.1
Process Precision
The measured mA value is rounded to p/- 0.1 mA resolution.
The measured mV value is rounded to p/- 10 mV resolution.
9.6.4.2
Process Sensor Trigger Function
The Sensor Trigger function is used to reset the IPSO min/max values as well as control the Calibration process.
Process Sensor Trigger Function
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
Reset
Min/Max
15
14
13
12
11
10
9
8
0
0
Calibration
Reset
Calibration
Status
Calibration
Mode
Capture
High
Capture
Low
Calibration
Start
Setting the Reset Min/Max bit to 1 will reset the Min/Max values recorded by the IPSO process. No User
Calibration process is supported on the Process inputs and all configuration bits should be written as 0.
32
|
P a g e