132
2. Spot check query function (Press the button on the display board to spot check the system parameters)
IEMP009(12,18,24)J3A-DCG026(36,53,71)
Sequence number Spot check parameter contents
Remarks
01
Indoor unit T1 temperature
Actual value, temperature accurate to 0.5
℃
02
Indoor unit T2 temperature
Actual value, temperature accurate to 0.5
℃
03
Outdoor unit T3 temperature
Actual value, temperature accurate to 0.5
℃
04
Outdoor unit T4 temperature
Actual value, temperature accurate to 0.5
℃
05
Outdoor unit TP temperature
Actual value, it can display three digits such
as 101
℃
06
Outdoor unit IPM temperature
Actual value, temperature accurate to 0.5
℃
07
Current compressor target frequency
Actual value
08
Current compressor operating frequency
Actual value
09
Current operating wind speed of internal fan
Actual value×10
10
Current operating wind speed of external fan
Actual value×10
11
Opening of electronic expansion valve of outdoor unit No electronic expansion valve
,
it shows "0"
12
Voltage
Actual value
13
current
Actual value
14
Indoor unit program version number
15
Indoor unit EEPROM parameter program version
number
16
Machine model
17
the last fault code
No fault display “--”
18
the last but one fault code
No fault display “--”
19
the last but two fault code
No fault display “--”
20
nd
End
IEMP031(36,42,48,60)J3A-DCG090(105,120,140,160)
Sequence number Spot check parameter contents
Remarks
1
Operation mode
(0 - standby; 1 - air supply; 2 - refrigeration; 3 -
heating; 4 - forced refrigeration; 6 -
dehumidification)
2
Operating wind speed and level
(0-shutdown; 2-low wind; 3-mid wind; 4-high
wind)
3
The number of HP of indoor unit‘s capacity
4
Total capacity demand of indoor unit
5
Capability requirements after outdoor unit
modification
6
Ts setting temperature
The actual value
7
T1 indoor temperature
The actual value
8
T2 or T2B temperature
The actual value
(
Heating display T2, other
display T2B
)
9
T3 pipe temperature
The actual value
10
T4 environment temperature
The actual value
11
T5 discharge temperature
The actual value
12
TF Module temperature
The actual value
13
TL Temperature of refrigerant radiation pipe
Refrigerant radiation pipe
14
The opening of Electronic expansion valve
The actual value×8
15
Actual current value
Содержание OTEC IEMP-D Series
Страница 1: ...IEMP D Series Ducted Fan Coil Technical Manual...
Страница 4: ...2 Part 1 General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 4...
Страница 17: ...17 ICHD031J0A DMG090...
Страница 18: ...18 ICHD036J0A DMG105 ICHD042J0A DMG120 ICHD048J0A DMG140...
Страница 19: ...19 ICHD060J0A DMG160...
Страница 29: ...36 IEMP031J3A DCG090 IEMP060J3A DCG160...
Страница 30: ...37 IEMP036J3A DCG105 IEMP042J3A DCG120 IEMP048J3A DCG140...
Страница 86: ...126 IEMP031 36 42 48 60 J3A DCG090 105 120 140 160...