109
2.2 Mount the unit
• Use the Φ10 lifting bolts (four).
• Removing the ceiling: Since the building structure is different, discuss building details with the interior
decoration workers.
a. Ceiling treatment: Reinforce the ceiling pedestal to make sure that the ceiling is level and to prevent ceiling
vibrations.
b. Cut off and dismantle the ceiling pedestal.
c. Reinforce the remaining surface after the ceiling is removed. Add further reinforcements to the pedestal on
two ends of the ceiling.
d. Once the main unit has been lifted and mounted, carry out the piping and wiring works within the ceiling.
Determine the outlet direction of the piping after the installation site has been finalized.
For a site where the ceiling is already available, first connect and put in position the refrigerant piping, water
discharge piping, connecting wires of the indoor unit and wired controller before you lift and mount the unit.
To match the existing structure, set the screw pitch according to the product dimensions shown below.
.
2.3 Lifting the IDU
• Mount the lifting bolt in the U-shaped groove to install the lifting lugs, lift the machine, and use the gradienter
to determine how level the device is.
• Fasten the nuts on the top.
>300mm
600mmx600mm
(accesshole)
>200mm
Содержание OTEC IEMP-D Series
Страница 1: ...IEMP D Series Ducted Fan Coil Technical Manual...
Страница 4: ...2 Part 1 General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 4...
Страница 17: ...17 ICHD031J0A DMG090...
Страница 18: ...18 ICHD036J0A DMG105 ICHD042J0A DMG120 ICHD048J0A DMG140...
Страница 19: ...19 ICHD060J0A DMG160...
Страница 29: ...36 IEMP031J3A DCG090 IEMP060J3A DCG160...
Страница 30: ...37 IEMP036J3A DCG105 IEMP042J3A DCG120 IEMP048J3A DCG140...
Страница 86: ...126 IEMP031 36 42 48 60 J3A DCG090 105 120 140 160...