110
2.4 Air inlet panel for air return plenum
Site adjustment of air return plenum:
There are two kinds of air return modes for this series of models. One is back return air which is the factory
default. The other is bottom air return which can be adjusted on-site. Refer to the following diagrams on the
adjustment method.
1. Remove back cover plate assembly
2. Install back cover plate assembly
Caution:
• In creating the air return plenum on the air inlet panel, make sure the air inlet grille is angled such that it is
parallel to the direction of the air inlet. See Figure 1.
• There should be no angle between the air inlet grille and the direction of the air inlet; otherwise the noise
level will increase. Figure 2 shows the incorrect way of making the air inlet panel.
• When the air outlet panel is connected to the air outlet flange of the unit body via the metallic air diffuser,
make sure that the sheet metal contact surface is properly sealed and insulated using sponge, as shown in
Figure 3.
2.5 Steps to dismantle the drain pan
The drain pan must first be removed during the maintenance of the internal unit assembly (make sure that
You need to add sponges to the air
outlet flange for insulation.
Metallic air diffuser
Figure 3
Figure 1
Figure 2
Air inlet direction
Air inlet direction
Air inlet grille
Air inlet grille
Содержание OTEC IEMP-D Series
Страница 1: ...IEMP D Series Ducted Fan Coil Technical Manual...
Страница 4: ...2 Part 1 General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 4...
Страница 17: ...17 ICHD031J0A DMG090...
Страница 18: ...18 ICHD036J0A DMG105 ICHD042J0A DMG120 ICHD048J0A DMG140...
Страница 19: ...19 ICHD060J0A DMG160...
Страница 29: ...36 IEMP031J3A DCG090 IEMP060J3A DCG160...
Страница 30: ...37 IEMP036J3A DCG105 IEMP042J3A DCG120 IEMP048J3A DCG140...
Страница 86: ...126 IEMP031 36 42 48 60 J3A DCG090 105 120 140 160...