Step Fifteen

Step Fourteen

C. Wiring to a Typical Programmable Logic Controller

-         +

+          -

DC Power

Supply

12-28 VDC

 

(+)

(-)

SHIELD

+         -

DC Power

Supply

12-28 VDC

 

TYpical PLC

6

5

4

3

2

1

0

A

(+)

(-)

Shield

WIRING

A. Wiring to a Omega LVCN-51 Controller

B. Wiring to a Typical Two-Wire Loop Powered Indicator

LATCH

ON  OFF

P W R

R E L AY  1

INVERT

DELAY

R E L AY  2

INVERT

DELAY

4           20          OP

E A S Y   CAL

UP

DOWN

SET

INPUT

0%

100%

OFF SET

SP

AN

RL

Y1

RL

Y2A

RL

Y2B

(+)

(-)

SHIELD

JWA mode

A. Fitting Selection:

Check the transmitter

part number to determine the required 2” fitting
thread type. The transmitter is commonly installed
in tank adapters, flanges, brackets or stand pipes. 

1. Adapter:

Select a tank adapter fitting with

minimal height so as to ensure that the
installed transducer will not be substantially
elevated into the fitting. Avoid tank adapter
styles with threads and/or pipe stops forward
of the installed transducer. 

2. Flange:

Tall flanges with narrow risers

impede the acoustic signal.  Select a fitting
with the right riser height versus inner diame-
ter geometry.  The transmitter may be elevat-
ed up to 12” (30 cm) in a 6” (15 cm) riser, 8”
(20 cm) in a 4” (10 cm) riser and 3” (7.6 cm)
in a 2” (5 cm) riser. 

3. Bracket:

The LVM-30 bracket or equivalent

can be used for open tank top installations

against the side wall.

4. Stand Pipe:

A stand pipe may be

used to dampen turbulence or separate
surface foam. Select a minimum 3” pipe
for the stand pipe.  The pipe length
should run the measurement span.  Cut a
45° notch at the bottom of the pipe and
drill a 1/4” pressure equalization hole
high in the dead band.

VACUUM

Do not install at

angle relative 

to the liquid

Do not install 

within 3” of 

tank side wall

Do not install 

with objects 

in the beam

Do not install 

in applications 

with vacuum 

Dead Band

Ventilation
Hole

Operational Range

Highest 
Liquid Level

Lowest 
Liquid Level

3" Minimum
Diameter

Warning

Omega ultrasonic transmitters have been optimized for use in
non-metallic fittings.  For best performance, avoid the use of
metal fittings.

Install the appropriate installation fitting. Make sure that the fit-
ting and transmitter threads are not damaged or worn. Install the
transmitter with the included Viton mounting gasket. Hand tight-
en the transmitter within the fitting. Perform an installed leak test
under normal process conditions prior to system start up.

Height

Inner Diameter

Adapter

Flange

Stand Pipe

Bracket

Gasket

Riser

INSTALLATION

Содержание LVU800 Series

Страница 1: ...erial number of the product under warranty and 3 Repair instructions and or specific problems relative to the product FOR NON WARRANTY REPAIRS consult OMEGA for current repair charges Have the followi...

Страница 2: ...volatile Supply voltage 12 28 VDC Loop resist 500 Ohms 24 VDC Signal output 4 20 mA two wire Signal invert 4 20 mA 20 4 mA Calibration Push button Fail safety Selectable 4 mA 20 mA 21 mA 22 mA or hold...

Страница 3: ...ten the transmitter within the fitting Always check for leaks prior to system start up Wiring and Electrical A supply voltage loop power of 12 28 VDC is used to power the LVU800 series The sensor circ...

Страница 4: ...Level has reached the programmed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNITS Selectable in Inches Centimeters or Percent The facto ry default is Inches E INCHES In...

Страница 5: ...emo ry after depressing the SELECT FAST key DD ERROR Indicates that the new value has NOT been saved in memory after depressing the SELECT FAST or EXIT key EE RUN When displayed if the user depresses...

Страница 6: ...R FILL H MinR E Change Display Mode To change the display to indicate the height of liquid follow the instructions below 1 Press the SELECT FAST button and hold it for 5 seconds until PROG appears 2 W...

Страница 7: ...will rotate between HEIGHT FILL H and REV mA 3 When HEIGHT appears press the SELECT FAST button The display will show a decimal reading in the selected UNITS 4 Press the UP DOWN buttons to increase or...

Страница 8: ...CT FAST button 3 The display will now rotate through 22mA 21mA 20mA 4mA and HOLD When you reach the desired setting press the SELECT FAST button to SAVE it You have successfully programmed the SAFE mo...

Страница 9: ...0 cm in a 4 10 cm riser and 3 7 6 cm in a 2 5 cm riser 3 Bracket The LVM 30 bracket or equivalent can be used for open tank top installations against the side wall 4 Stand Pipe A stand pipe may be use...

Страница 10: ...T FAST TROUBLESHOOTING Transmitter LVU816 LVU826 LVU832 4 mA Setting 16 4 5m 26 2 8m 32 8 10m 20 mA Setting 8 10 cm 8 20 cm 12 30 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA...

Отзывы: