manualshive.com logo in svg
background image

Step Ten

Step Eleven

PROGRAMMING

I. Programming REV mA (Optional):

In factory default, 

t

he

transmitter operates with 4 mA at the maximum range (MaxR), and

20 mA at the dead band (MinR). Using the menu item REV mA, you

can change the unit to reverse this to 20 mA at the furthest distance

(MaxR) and 4 mA at the closest distance (MinR). 

NOTE: You must set HEIGHT and FULL R prior to reversing

the 4 and 20 mA.  Regardless of which mode you are in (Norm

or Rev), changes to the HEIGHT or FULL R are always with

respect to the original settings programmed.

NOTE: Any changes to the HEIGHT will effect the FULL R

value.  The FULL R will stay at the same physical level in the

tank.  An increase to the HEIGHT value will result in an equal

increase to the FULL R value.  A decrease to the HEIGHT value

will result in an equal decrease to the FULL R value.

4 mA

20 mA

SELECT

FAST

SELECT

FAST

SELECT

FAST

20 mA

4 mA

Normal mA Mode

MaxR (4 mA) set at empty tank 

and MinR (20 mA) set at full tank.

Reverse mA Mode

MaxR (20 mA) set at empty tank 
and MinR (4 mA) set at full tank. 

PROGRAMMING

G. Programming HEIGHT:

To change HEIGHT 4 mA value.

1. Press the SELECT/FAST button and hold it for 5 seconds until

PROG appears.

2. When TANK appears, press the SELECT/FAST button. The dis-

play will rotate between HEIGHT, FILL H and REV mA.

3. When HEIGHT appears, press the SELECT/FAST button. The

display will show a decimal reading in the selected UNITS. 

4. Press the UP/DOWN buttons to increase or decrease this value to the

distance from the transducer face to the bottom of the tank.  NOTE:

Simultaneously holding down the SELECT/FAST button while press-

ing the UP or DOWN button will increase the speed of the display. 

5. When you have reached the desired value, press SELECT/FAST

to SAVE.

You have successfully programmed the HEIGHT or 4 mA value.

H. Programming FILL H:

To change FILL H 20 mA value.

1. Press the SELECT/FAST button and hold it for 5 seconds until

PROG appears.

2. When TANK appears, press the SELECT/FAST button. The dis-

play will rotate between HEIGHT, FILL H and REV mA.

3. When FULL H appears, press the SELECT/FAST button. The dis-

play will show a decimal reading in the selected UNITS. 

4. Press the UP/DOWN buttons to increase or decrease this value to

the distance from the bottom of the vessel to the full point (typi-

cally the straight wall height). 

5. When you have reached the desired value, press SELECT/FAST

to SAVE it.

You have successfully programmed the FILL H or 20mA value.

NOTE: You can increase the speed at which the display changes

by pressing the SELECT/FAST button while simultaneously hold-

ing down the UP or DOWN button.

SELECT

FAST

SELECT

FAST

SELECT

FAST

UP

DOWN

SELECT

FAST

SELECT

FAST

SELECT

FAST

UP

DOWN

Содержание LVU800 Series

Страница 1: ...erial number of the product under warranty and 3 Repair instructions and or specific problems relative to the product FOR NON WARRANTY REPAIRS consult OMEGA for current repair charges Have the followi...

Страница 2: ...volatile Supply voltage 12 28 VDC Loop resist 500 Ohms 24 VDC Signal output 4 20 mA two wire Signal invert 4 20 mA 20 4 mA Calibration Push button Fail safety Selectable 4 mA 20 mA 21 mA 22 mA or hold...

Страница 3: ...ten the transmitter within the fitting Always check for leaks prior to system start up Wiring and Electrical A supply voltage loop power of 12 28 VDC is used to power the LVU800 series The sensor circ...

Страница 4: ...Level has reached the programmed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNITS Selectable in Inches Centimeters or Percent The facto ry default is Inches E INCHES In...

Страница 5: ...emo ry after depressing the SELECT FAST key DD ERROR Indicates that the new value has NOT been saved in memory after depressing the SELECT FAST or EXIT key EE RUN When displayed if the user depresses...

Страница 6: ...R FILL H MinR E Change Display Mode To change the display to indicate the height of liquid follow the instructions below 1 Press the SELECT FAST button and hold it for 5 seconds until PROG appears 2 W...

Страница 7: ...will rotate between HEIGHT FILL H and REV mA 3 When HEIGHT appears press the SELECT FAST button The display will show a decimal reading in the selected UNITS 4 Press the UP DOWN buttons to increase or...

Страница 8: ...CT FAST button 3 The display will now rotate through 22mA 21mA 20mA 4mA and HOLD When you reach the desired setting press the SELECT FAST button to SAVE it You have successfully programmed the SAFE mo...

Страница 9: ...0 cm in a 4 10 cm riser and 3 7 6 cm in a 2 5 cm riser 3 Bracket The LVM 30 bracket or equivalent can be used for open tank top installations against the side wall 4 Stand Pipe A stand pipe may be use...

Страница 10: ...T FAST TROUBLESHOOTING Transmitter LVU816 LVU826 LVU832 4 mA Setting 16 4 5m 26 2 8m 32 8 10m 20 mA Setting 8 10 cm 8 20 cm 12 30 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA...

Отзывы: