manualshive.com logo in svg
background image

Step Two

SAFETY

Step Three

OVERVIEW

A. Application:

The general-purpose ultrasonic transmitter pro-

vides non-contact level detection up to 32.8’ or 10m. The transmitter

is well suited for a wide range of corrosive, waste and slurry type

media, and is broadly selected for atmospheric bulk storage, day tank

and waste sump applications.

B. Part Number:

The part and serial numbers are located on the

wrench flat. Check the part number on the product label and confirm

which of the below model configurations you have purchased:

Part Number

Range

Supply

Mount

LVU816

16.4’ (5 m)

12-28 VDC

2” NPT

LVU816G

16.4’ (5 m)

12-28 VDC

2” G

LVU826

26.2’ (8 m)

12-28 VDC

2” NPT

LVU826G

26.2’ (8 m)

12-28 VDC

2” G

LVU832

32.2’ (10 m)

12-28 VDC 

2” NPT

LVU832G

32.2’ (10 m)

12-28 VDC 

2” G

C. NEMA 4X Enclosure:

The NEMA 4X (IP65) enclosure has

a flip cover with two 1/2” NPT female conduit ports and an internal

terminal strip for wiring.  To open the enclosure, you will need a small

small screwdriver.  Insert the tool into the hole located at the top edge

of the enclosure and turn counter-clockwide.  Rotate the hinged cover

up for 135° access to the faceplate screen and terminal strip. 

About this Manual:

PLEASE READ THE ENTIRE MANU-

AL PRIOR TO INSTALLING OR USING THIS PRODUCT.  This

manual includes information on then LVU800 Ultrasonic Level

Transmitter from OMEGA. Please refer to the part number located

on the transmitter label to verify the exact model configuration

which you have purchased.

User’s Responsibility for Safety:

OMEGA manufactures

a broad range of level sensing technologies. While each of these

sensors is designed to operate in a wide variety of applications, it is

the user’s responsibility to select a sensor model that is appropriate

for the application, install it properly, perform tests of the installed

system, and maintain all components. The failure to do so could

result in property damage or serious injury. 

Proper Installation and Handling:

Only properly trained

staff should install and/or repair this product. Install the transmitter

with the Viton gasket and never overtighten the transmitter within

the fitting. Always check for leaks prior to system start-up.

Wiring and Electrical:

A supply voltage (loop power) of 12

-28 VDC is used to power the LVU800 series.  The sensor circuit

should never exceed a maximum of 28 volts DC. Electrical wiring

of the sensor should be performed in accordance with all applica-

ble national, state, and local codes.

Material Compatibility:

The LVU800 series enclosure is

made of a flame retardant Polycarbonate (PC/ABS FR).  The trans-

ducer is made of Polyvinylidene Fluoride (PVDF).  Make sure that

the model which you have selected is chemically compatible with

the application media and it’s environment.

Enclosure:

While the transmitter housing is liquid-resistant the

LVU800 series is not designed to be operational when immersed. It

should be mounted in such a way that the enclosure and transduc-

er do not come into contact with the application media under nor-

mal operational conditions.

Make a Fail-Safe System:

Design a fail-safe system that

accommodates the possibility of transmitter and/or power failure.

OMEGA recommends the use of redundant backup systems and

alarms in addition to the primary system.

Flammable, Explosive or Hazardous Applications:

Do not use the LVU800 series of general purpose transmitters with-

in classified hazardous environments. 

Warning

Always use the Viton gasket when installing the LVU800 series
transmitter in its fitting, and always connect the shield wire to
the common ground.

Handling Static-Sensitive Circuits/Devices

When handling the transmitter, the technician should follow
these guidelines to reduce any possible electrostatic charge
build-up on the technicians body and the electronic part.

1. Always touch a known good ground source before handling the

part.  This should be repeated while handling the part and more
frequently after sitting down from a standing position, sliding
across the seat or walking a distance.

2. Avoid touching electrical terminals of the part unless making connections.

3. DO NOT open the unit cover until it is time to calibrate.

Before closing the enclosure, make sure that the enclosure gasket is
properly seated, and that any conduit fittings, liquid tight cable con-
nectors and/or plugs are properly installed and sealed. 

Closed

Open

Содержание LVU800 Series

Страница 1: ...erial number of the product under warranty and 3 Repair instructions and or specific problems relative to the product FOR NON WARRANTY REPAIRS consult OMEGA for current repair charges Have the followi...

Страница 2: ...volatile Supply voltage 12 28 VDC Loop resist 500 Ohms 24 VDC Signal output 4 20 mA two wire Signal invert 4 20 mA 20 4 mA Calibration Push button Fail safety Selectable 4 mA 20 mA 21 mA 22 mA or hold...

Страница 3: ...ten the transmitter within the fitting Always check for leaks prior to system start up Wiring and Electrical A supply voltage loop power of 12 28 VDC is used to power the LVU800 series The sensor circ...

Страница 4: ...Level has reached the programmed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNITS Selectable in Inches Centimeters or Percent The facto ry default is Inches E INCHES In...

Страница 5: ...emo ry after depressing the SELECT FAST key DD ERROR Indicates that the new value has NOT been saved in memory after depressing the SELECT FAST or EXIT key EE RUN When displayed if the user depresses...

Страница 6: ...R FILL H MinR E Change Display Mode To change the display to indicate the height of liquid follow the instructions below 1 Press the SELECT FAST button and hold it for 5 seconds until PROG appears 2 W...

Страница 7: ...will rotate between HEIGHT FILL H and REV mA 3 When HEIGHT appears press the SELECT FAST button The display will show a decimal reading in the selected UNITS 4 Press the UP DOWN buttons to increase or...

Страница 8: ...CT FAST button 3 The display will now rotate through 22mA 21mA 20mA 4mA and HOLD When you reach the desired setting press the SELECT FAST button to SAVE it You have successfully programmed the SAFE mo...

Страница 9: ...0 cm in a 4 10 cm riser and 3 7 6 cm in a 2 5 cm riser 3 Bracket The LVM 30 bracket or equivalent can be used for open tank top installations against the side wall 4 Stand Pipe A stand pipe may be use...

Страница 10: ...T FAST TROUBLESHOOTING Transmitter LVU816 LVU826 LVU832 4 mA Setting 16 4 5m 26 2 8m 32 8 10m 20 mA Setting 8 10 cm 8 20 cm 12 30 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA...

Отзывы: