Step Thirteen

Step Twelve

L. Programming TG CAL EMPTY Tank:

With the tank

EMPTY or the liquid in a low level state, apply power to the trans-

mitter. Begin programming after WARMUP. 

1. Press the SELECT/FAST button and hold it for 5 seconds until

PROG appears.

2. When TG CAL appears, press the SELECT/FAST button. The

display will rotate between FULL and EMPTY. 

3. When EMPTY appears, press the SELECT/FAST button. WAIT

will be displayed followed by SAVED. 

You have successfully programmed the EMPTY or 4 mA value.

M. Programming TG CAL FULL Tank:

With the tank FULL,

or the liquid in a high level state, apply power to the transmitter.

Begin programming after WARMUP.

1. Press the SELECT/FAST button and hold it for 5 seconds until

PROG appears.

2. When TGCAL appears, press the SELECT/FAST button. The dis-

play will rotate between FULL and EMPTY.

3. When FULL appears, press the SELECT/FAST button, WAIT will

be displayed followed by SAVED. 

You have successfully programmed the FULL or 20 mA value.

PROGRAMMING

SELECT

FAST

SELECT

FAST

SELECT

FAST

SELECT

FAST

SELECT

FAST

SELECT

FAST

Note: The display will now indicate LEVEL height in the RUN

mode.

J. Programming SAFE Mode:

To change SAFE mode. 

1. Press the SELECT/FAST button and hold it for 5 seconds until

PROG appears.

2. When SAFE appears, press the SELECT/FAST button. 

3. The display will now rotate through 22mA, 21mA, 20mA, 4mA

and HOLD. When you reach the desired setting, press the

SELECT/FAST button to SAVE it..

You have successfully programmed the SAFE mode.

K. Programming Target Calibration (Optional):

The

transmitter’s 4 mA and 20 mA set points can be target calibrated ON

the tank by raising and lowering the liquid level, or OFF the tank

using the distance to a flat reflective target such as a wall. Generally,

target calibration is done ON the tank. To do so, follow the EMPTY

and FULL tank programming steps on the next page.

NOTE: A transmitter installed on a tank operating in the facto-

ry default RUN mode will display the distance from the bottom

of the sensor to the liquid surface. The value will decrease as the

tank is filled or increase as the tank is emptied. Make sure that

you do not overflow the tank or completely empty the tank while

moving the liquid level to the desired high or low set point dis-

tance for target calibration.

TG CAL:

Allows the user to use an unknown distance for setting

of the 4 mA and 20 mA span. 

FULL:

Target calibration technique that allows the user to enter

the present distance from the

transducer face to the liquid or a

reflective target as the 20 mA

(FULL) set point

EMPTY:

Target calibration

technique that allows the user to

enter the present distance from

the transducer face to the liquid

or a reflective target as the 4 mA

(EMPTY) set point. 

SELECT

FAST

SELECT

FAST

EMPTY

FULL

PROGRAMMING

Содержание LVU800 Series

Страница 1: ...erial number of the product under warranty and 3 Repair instructions and or specific problems relative to the product FOR NON WARRANTY REPAIRS consult OMEGA for current repair charges Have the followi...

Страница 2: ...volatile Supply voltage 12 28 VDC Loop resist 500 Ohms 24 VDC Signal output 4 20 mA two wire Signal invert 4 20 mA 20 4 mA Calibration Push button Fail safety Selectable 4 mA 20 mA 21 mA 22 mA or hold...

Страница 3: ...ten the transmitter within the fitting Always check for leaks prior to system start up Wiring and Electrical A supply voltage loop power of 12 28 VDC is used to power the LVU800 series The sensor circ...

Страница 4: ...Level has reached the programmed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNITS Selectable in Inches Centimeters or Percent The facto ry default is Inches E INCHES In...

Страница 5: ...emo ry after depressing the SELECT FAST key DD ERROR Indicates that the new value has NOT been saved in memory after depressing the SELECT FAST or EXIT key EE RUN When displayed if the user depresses...

Страница 6: ...R FILL H MinR E Change Display Mode To change the display to indicate the height of liquid follow the instructions below 1 Press the SELECT FAST button and hold it for 5 seconds until PROG appears 2 W...

Страница 7: ...will rotate between HEIGHT FILL H and REV mA 3 When HEIGHT appears press the SELECT FAST button The display will show a decimal reading in the selected UNITS 4 Press the UP DOWN buttons to increase or...

Страница 8: ...CT FAST button 3 The display will now rotate through 22mA 21mA 20mA 4mA and HOLD When you reach the desired setting press the SELECT FAST button to SAVE it You have successfully programmed the SAFE mo...

Страница 9: ...0 cm in a 4 10 cm riser and 3 7 6 cm in a 2 5 cm riser 3 Bracket The LVM 30 bracket or equivalent can be used for open tank top installations against the side wall 4 Stand Pipe A stand pipe may be use...

Страница 10: ...T FAST TROUBLESHOOTING Transmitter LVU816 LVU826 LVU832 4 mA Setting 16 4 5m 26 2 8m 32 8 10m 20 mA Setting 8 10 cm 8 20 cm 12 30 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA...

Отзывы: