34

DPF20 Frequency, rate, total or period counter

Instruction Manual

2.5 Module S2

Module  S2  provides  1  RS-232  ASCII  communications  port,  to  install  in 

DPF20 digital panel meters. Protocol specifications are the same as with 

module S4 

(see section 2.4)

, with only difference that the physical bus is 

RS-232 instead of RS-485.
S2 modules allow for point-to-point communication over RS-232 and also 

allow for multinode communication over RS-232 using a ‘Daisy-Chain’ type 

of connection.
Terminals RX1 and TX1 are for connection to the RS-232 bus. Terminals 

RX2 and TX2 are for RS-232 multinode connection. Frames received on 

RX1  with  destination  address  different  than  the  local  instrument’s  ad

-

dress, will be retransmitted over the TX2 terminal. In a similar way, frames 

received from RX2 with destination address other than the local address, 

will be retransmitted over TX1 terminal.
Up to a maximum of 3 S4 modules can be installed in a single instrument, 

all modules isolated between them and isolated from all other circuits.
Modules S2 can be ordered pre-installed into a DPF20 digital panel meter, 

or standalone for delayed installation, as they do not require soldering or 

special configuration.

Option 

S2

Output type 

RS-232 ASCII communication port

Bus 

RS-232

Speed 

57.6 Kbps to 600 bps

Data format 

8n1 (standard), 8o1, 8n2, 8e1

Protocol 

ASCII

Architecture 

‘master - slave’

Addresses 

01 to 31

‘Broadcast’ address 

128

Registers 

see section 

2.4.1

Isolation 

1000 Vdc

Configuration  

3 button front keypad

Temperature  

operation from 0 to 50 ºC

 

 

storage from -20 to +70 ºC

Installation allowed at 

‘Opt.1’, ‘Opt.2’, ‘Opt.3’

Power

Opt.2

Opt.1

Op

t.3

A B C D E

ABCDE

Signal

A B C D E

Rear view DPF20

Module

Connections

Module S2 - RS-232 ASCII

Terminal A 

Tx2 

Terminal B 

Rx2

Terminal C 

Tx1

Terminal D 

Rx1

 

Terminal E 

GND

Table 16 - Connection terminals

Option  

R2, R4, R6

Output type 

relay (2, 4 and 6 relays)

Relay type 

3 contacts (NC, NO, common)

Maximum current 

6 A per relay (resistive load)

Maximum voltage* 

250 Vac continuous

* terminals approved for 300

V (as per UL1059, groups B and D) and 

160

V (as per VDE at CAT-III and pollution degree 3).

Isolation 

2500 Veff

Type of terminal 

plug-in screw terminal

 

 

pitch 5.08 mm

Installation allowed at 

‘Opt.1’

   Module R2 

occupies Opt.1 (2 relays)

   Module R4 

occupies Opt.1 and Opt.2 (4 relays)

   Module R6 

occupies Opt.1, Opt.2 and Opt.3 (6 relays)

Modules R2, R4 and R6 provide 2, 4 and 6 relay outputs, to install in 

DPF20 digital panel meters.
Configuration is performed from the frontal keypad of the meter, by 

setting the parameters at the ‘Opt.1’ configuration menu (not from 

the alarm configuration menu (‘ALr.1’, ‘ALr.2’ o ‘ALr.3’) of the instru

-

ment).
The menu allows to configure the setpoint, hysteresis, independent 

activation and deactivation delays, and a second setpoint to create 

alarm windows.
Only 1 modules R2, R4 or R6 can be installed in a single instrument,  

as the are not compatible with themselves (2 modules R2 are not ac

-

cepted) and are not compatible with modules R1, T1 or SSR.
Modules R2, R4 and R6  are isolated against all other instrument cir

-

cuits.
Modules R2, R4 and R6 can be ordered pre-installed into a DPF20 

digital panel meter, or standalone for delayed installation, as they do 

not require soldering or special configuration.

2.6 

Modules R2, R4 and R6

Rear view DPF20

Power

Opt.2

Opt.1

Op

t.3

A B C D E F

Signal

G H I J K L

MNOPQR

Relay

Common

Normally Open (NO) Normally Closed (NC)

relay 1

A

B

C

relay 2

D

E

F

relay 3

G

H

I

relay 4

J

K

L

relay 5

M

N

O

relay 6

P

Q

R

Table 17 - Connection terminals

Содержание DPF20 Series

Страница 1: ...ail info omega com For latest product manuals www omegamanual info DPF20 Series Panel Meter for Frequency Rate Total or Period Counter 6 Digit 1 8 DIN Panel Mount TM Shop online at omega com User sGui...

Страница 2: ...eserves the right to alter specifications without notice Servicing North America U S A Omega Engineering Inc Headquarters Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA C...

Страница 3: ...ctive it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to mishandling improper interfacing o...

Страница 4: ...ghtness levels Index 1 Panel meter DPF20 4 1 1 How to order 5 1 2 Impulse counter modes 5 1 3 Ratemeter modes 5 1 4 Periodmeter mode 5 1 5 Functions included 5 1 6 Front view 6 1 7 Power connections 6...

Страница 5: ...tor 1 to 999999 and configurable divider factor 1 to 999999 For low frequency applications the SLOW mode provides the best response time for each application see section 1 15 Maximum frequency up to 5...

Страница 6: ...r menu entry will configure the sen sor parameters to the values indicated in the table The table also indicates the typical con nections for each type of sensor Param eters can be manually modified C...

Страница 7: ...control options relays analog outputs serial communi cations see section 2 Mechanical mounting panel connections plug in screw terminal housing material ABS polycarbonate V0 weight 150 grams front siz...

Страница 8: ...the instrument restart power up or configuration change is used for internal initialization and will not be counted as impulse 1 14 Function cycle counter 1 15 SLOW mode The trigger level is automati...

Страница 9: ...nctions as a ENTER key It selects and accesses the menu option currently dis played At menus with numerical value entries it validates the num ber displayed Key UP 5 the UP 5 key gives access to the f...

Страница 10: ...eter mode Impulses input at channel A Channel B disabled Access the Decimal point dP menu to select the decimal point position Move the decimal point by pressing the LE 3 key Configure the function mo...

Страница 11: ...unting when channel B is at logical state 1 Select on_0 to inhibit the counting when channel B is at logical state 0 1 19 4 Configuration for cnI 3 Configuration menu for mode counter control add subs...

Страница 12: ...5 for more in formation on the SLoW mode in case of unstable signals activate the average filter AVr func tion It activates a recursive filter on the reading the filter is stronger for higher values f...

Страница 13: ...ncies activate the SLoW parameter configuring the tIME parameter between 1 and 1000 seconds Configure the nuMb parameter between 1 and 32 impulses See section 1 15 for more in formation on the SLoW mo...

Страница 14: ...on for reset channel Act r configures the activa tion of the reset channel by rising edge on_h or by falling edge on_0 Excitation voltage V EXc configures the value of the excita tion voltage at 5 Vdc...

Страница 15: ...lue from 0 0 to 99 9 seconds at Deactivation delay dEL 1 configure the delay to apply before alarm deactivation The deactivation delay starts counting when the setpoint value plus the hysteresis value...

Страница 16: ...allows to visualize and modify the alarm2 setpoint through the fast access menu the Setpoint3 ALr3 function allows to visualize and modify the alarm3 setpoint through the fast access menu the Memory...

Страница 17: ...ord At the Factory reset FAct menu select yes to load the default factory configuration for the instrument see section 1 21 1 19 20 Factory reset 1 19 21 Firmware version The Counter overrange c orG a...

Страница 18: ...999999 Conf counter inhibition Multiplier Divider Preset Preset value 199999 to 999999 Mode Up Down Inhibition Inhibits if chan nel B is high Inhibits if chan nel B is 0 Vdc Multiplier 1 to 999999 Div...

Страница 19: ...level from 0 0 Vdc a 3 9 Vdc See section 1 15 for Trigger Sense utility Pull down No pull resistor Pull up Pulls on reset Pulls on channel B Pull down No pull resistor Pull up Pull down No pull resis...

Страница 20: ...ximum Memory of minimum Setpoint 1 Setpoint 2 Setpoint 3 Memory of cycles Preset value On power up Delay Seconds Reset Key LE Front reset Alarm unlock No function Counter overrange Flash To zero To pr...

Страница 21: ...5 Vdc Antirrebound filter 0 mSeconds Tools Fast access Key UP off On Power Up Delay 0 seconds Key LE reset function Memory of maximum 199999 Memory of minimum 999999 Memory of cycles 0 Counter overran...

Страница 22: ...rectly connected to the pins on the display module Place all the set into the housing assuring that the modules correctly fit into the internal guiding slides of the housing Once introduced place agai...

Страница 23: ...the instrument In case of fire disconnect the instrument from the power line fire alarm according to local rules disconnect the air conditioning attack fire with car bonic snow never with water 1 24...

Страница 24: ...g in screw terminal pitch 5 08 mm Installation allowed at Opt 1 Opt 2 Opt 3 Option R1 Output type relay Relay type 3 contact relay NC NO common Maximum current 8 A resistive load Maximum voltage 250 V...

Страница 25: ...setting the parameters at the options configuration menu Opt 1 Opt 2 or Opt 3 depending on the position the module is installed The output signal is proportional to the instrument reading and it can b...

Страница 26: ...ent Reading Analog output Example analog output in 4 20 mA associated to a reading of 50 0 to 100 0 50 0 100 0 4 mA 20 mA d Lo 50 0 d hI 100 0 Ao hI 20 00 Ao Lo 4 00 Scaling Mode 4 20 mA Mode in case...

Страница 27: ...9999 9999 to 1999 10 SETPOINT2_H 16 bits 11 SETPOINT3_L Setpoint 3 value 16 bits 999999 to 199999 9999 to 1999 12 SETPOINT3_H 16 bits 13 STATUS Alarm status Instrument status 16 bits same as display b...

Страница 28: ...to load the de fault factory configuration for the instrument the Version VEr menu informs of the current firmware version installed in the module The Modbus RTU protocol defines the following scenar...

Страница 29: ...g to R5 and R6 Register R7 and R8 SETPOINT1_L and SETPOINT1_H Contains the setpoint value of alarm 1 codified in two registers of 16 bits each Possible values are from 999999 to 199999 Decimal point p...

Страница 30: ...5 ASCII Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND Table 13 Connection terminals Power Opt 2 Opt 1 Opt 3 B A G B A G Signal B A G Rear view DPF20 2 4 1 Acce...

Страница 31: ...grouped inside the Tools TooL menu the Decimal point dP menu is provided for compatibility with ancient hardware that does not support decimal point retransmis sion By default select Automatic Auto If...

Страница 32: ...apply see section 2 4 8 ETX End of frame 1 byte n 9 does not apply 3 Table 15 Description of the bytes for the ASCII frame Section Trail Contains the CRC code and the end of frame byte ETX Real value...

Страница 33: ...frame and the Slave replies to the Master with a PONG frame Frames PING 32 and PONG 33 2 4 7 Frame examples Frames RD 36 and ANS 37 Example Master address 0 requests the value of register 0 dis play...

Страница 34: ...C D E Rear view DPF20 Module Connections Module S2 RS 232 ASCII Terminal A Tx2 Terminal B Rx2 Terminal C Tx1 Terminal D Rx1 Terminal E GND Table 16 Connection terminals Option R2 R4 R6 Output type rel...

Страница 35: ...s when the reading has passed the setpoint value plus the hysteresis value at Delay 0 dEL 0 assign the delay to be applied before alarm activation The activation delay starts counting when the setpoin...

Страница 36: ...nclipped Front filter is slightly moved to the front on each corner It can now be removed by hand C 1 C 2 Unclipped Unclipped C 3 D B C A C Repeat with all clips Place a flat screw driver at the first...

Страница 37: ...e fitted or not fitted Fully insert corner X into the housing See at image B 2 that the filter is not yet clipped only corner X is completely fitted Corner Y can be also fitted or not fitted it is not...

Страница 38: ...38 DPF20 Frequency rate total or period counter Instruction Manual...

Страница 39: ...39 DPF20 Frequency rate total or period counter Instruction Manual...

Страница 40: ...Air Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps I...

Отзывы: