16

 Limits of temperature ranges 

Different input sensors have different application ranges (e.g.: J type factory setting is -100 ~ 1200

), adjust parameters 

  (upper 

limit) / 

  (lower limit) in Initial Setting Mode. 

If lower limit is altered to 0 and upper limit is altered to 200, the limit function will be enabled in the following conditions:   

When setting the SV value, the limits may set for 0~200

In ON-OFF, PID, FUZZY and Self-Tuning control conditions, the control output will be forced to shut off if the PV value exceeds the
upper/lower limit. (Alarm output is still normal)

 User Setting of F1, F2 function keys 

In the Operation Mode, (PV/SV display mode), pressing a function key more than 3 seconds will prompt you to the setting of the following 
functions; press 

 

  keys to make a selection. 

Function 

Description 

MENU 

When in a screen other than the PV/SV display mode, pressing F1/F2 key continuously may save the setting, to quickly 

switch the menu screen 
(When the screen shows KEY SAVE, the menu screen is saved) 

AT 

Selecting this function, F1 / F2 button can be used for quick ON / OFF operation of AT function 

R-S

Selecting this function, F1 / F2 button can be used to switch between RUN/STOP status. 

PROG 

Selecting this function, F1 / F2 button can be used to switch between RUN/HOLD status. 

ATMT 

Selecting this function, F1 / F2 button can be used to switch between PID and MANUAL control mode 

ALRS 

Selecting this function, F1 / F2 button can be used to reset Alarm Hold status.

 

SV2 

Selecting this function, F1 / F2 button can be used to switch between SV1/SV2.

 

For disabling F1/F2 function, please select 

MENU

  without saving any menu screen. 

 Edit a self-defined Menu Screen 

Hidden MENU setting: Lock all buttons by adjusting parameter 

  to 

  in 

Operation Mode

. At the same time press 

and 

    keys for 3 seconds to display 

  , and enter Password-1. The screen will show menu number 

, see the following 

table for details. Select “Hide” to hide the Menu. 

Menu Layer setting: Lock all buttons by adjusting parameter 

  to 

  in 

Operation Mode

. At the same time press 

and 

    keys for 3 seconds to display 

  , and enter Password-2. The screen will show menu number 

, see the following 

table for details. Selectable items are NOR= display layers; ADJ= adjust layers; SET= set layers. 

Menu layer reset: Lock all buttons by adjusting parameter 

  to 

  in 

Operation Mode

. At the same time press 

    and 

  keys for 3 seconds to display 

  , and enter Password-3. The screen displays 

  (Level reset) parameters, select 

  to reset all menu layers to default setting. 

RUN layer 

Adjust layer 

Setting layer 

Menu No. 

Corresponding menu 

Menu No. 

Corresponding menu

Menu No. 

Corresponding menu

M101 

M201 

M301 

M102 

M202 

M302 

M103 

M203 

M303 

M104 

M204 

M304 

M105 

M205 

M305 

M106 

M206 

M306 

M107 

M207 

M307 

M108 

M208 

M308 

M109 

M209 

M309 

M110 

M210 

M310 

M111 

M211 

M311 

M112 

M212 

M312 

M113 

M213 

M313 

M114 

M214 

M314 

Содержание CND3 Series

Страница 1: ...CND3 Series Temperature Controller www omegamanual info Shop online at omega com For latest product manuals User sGuide e mail info omega com...

Страница 2: ...rves the right to alter specifications without notice U S A Headquarters Servicing North America Omega Engineering Inc Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Cana...

Страница 3: ...or connecting the thermocouple wires 6 Please use wires with resistance when extending or connecting a platinum resistance thermometer RTD 7 Please keep the wire as short as possible when wiring a pl...

Страница 4: ...Note Not all combinations may be available Check website under All Models to see list of available models...

Страница 5: ...perature 20 C 65 C Altitude Max 2000m Relative Humidity 35 80 RH non condensing Operation There are three modes of operation operation regulation and initial setting When power is applied controller g...

Страница 6: ...for the selection of Thermocouple or Platinum Resistance types PT TEMP UNIT Set temperature unit it wil not be displayed when in analog input mode TEMP HIGH Set up upper temperature limit the upper li...

Страница 7: ...will select P value accordingly 47 6 I Integral Time Setting display when Crtl PID FUZZY 2PID this parameter is set automatically when TUNE AT Set I value according to the selection of PID No n 0 5 Wh...

Страница 8: ...eters into the selected PID group Select the n th PID n 0 5 press to set 0 5 th PID parameters Set up the 0 th PID temperature value press Set up the 5 th PID temperature value press Set up the 0 th p...

Страница 9: ...to change the PV and SV display unit select decimal point and switch between F In Operation Mode SP 1 displays decimal place ex 25 5 degree SP 0 displays integral number ex 25 degree In Initial Settin...

Страница 10: ...put 4 20mA or linear voltage output 0 10V user s desire output value can be attained by using compensation function For example the analog output 1 can be adjusted in and parameters in Regulation Mode...

Страница 11: ...ent output L Linear voltage output S SSR output SV 3 rd digit indicates the function of accessory 2 N No function C CT measure E EVENT1 input R REMOTE input SV 4 th digit indicates the function of acc...

Страница 12: ...e Some of the terms are explained as follows a Initial pattern set the program to start running at a sequential number of patterns b Initial Step set the program to start running at a sequential numbe...

Страница 13: ...Y position of parameter in Initial Setting Mode e g xxxY Y is 0 or 1 0 normal 1 power off saving Note When any settings or changes of the program parameters are made please save the settings changes t...

Страница 14: ...adjustment by parameter in Regulation Mode Remote lower limit Setting Remote lower limit by parameter in Regulation Mode Remote higher limit Setting Remote higher limit by parameter in Regulation Mode...

Страница 15: ...Initial Setting Mode To set for heating or cooling control Select desired output control by parameter in Initial Setting Mode If no board is inserted in Output2 selection items are H1 C1 H for heating...

Страница 16: ...and the AT LED in the panel goes out The calculated PID parameters are displayed in and of which their content can be revised by the user Automatic switching over Multiple PID sets Set parameter to 0...

Страница 17: ...g Set a value corresponding to Y position by parameter in Initial Setting Mode such as xxYx Y can be 0 or 1 0 30A 1 100A CT2 100A setting Set a value corresponding to Y position by parameter in Initia...

Страница 18: ...on F1 F2 button can be used to switch between PID and MANUAL control mode ALRS Selecting this function F1 F2 button can be used to reset Alarm Hold status SV2 Selecting this function F1 F2 button can...

Страница 19: ...will return to PV SV display mode 3 Enter the new password two times in the screen The screen will return to PV SV display mode with the keys unlocked If the two entries of password are not the same...

Страница 20: ...if PV value is lower than the setting value SV AL H This alarm output is OFF when PV value is higher than the setting value SV AL L ON OFF SV AL H SV AL L SV 9 Disconnection Alarm This alarm output op...

Страница 21: ...PV Measuring unit is 0 1 updated one time in 0 1 second The following reading value display indicates error occurs 8002H Initial process Temperature value is not got yet 8003H Temperature sensor is n...

Страница 22: ...r 0 15 1032H Remaining time of the executed step second Only read 1033H Remaining time of the executed step minute Only read 1034H No of currently executed step Only read 1035H No of currently execute...

Страница 23: ...Linear Output 2 Adjust current 1scale 1 A Adjust voltage 1scale 1mV 1119H Adjust Lower Limit of Analog Linear Output 2 Adjust current 1scale 1 A Adjust voltage 1scale 1mV 111AH Adjust Retransmission...

Страница 24: ...Starting data address 10H 08H Starting data address 10H 08H 00H 10H 01H 10H 01H 10H Number of data word Bit 00H 00H Start address data 1000H 081xH 01H 17H Data content 03H FFH Data content 03H FFH 02H...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...http www omega com to contact OMEGA Engineering Inc 800 Connecticut Ave Suite 5N01 Norwalk CT 06854 USA Customer Service 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada on...

Отзывы: