11

the start status, the program will start running from the initial pattern and initial step.   
When setting control is in pause control and temperature is controlled at the setting value before the stop, by re-selecting 
the start status, the program will start running from the step where the program was paused and carry out the remaining 
part. 

Set parameter

  to 

  In 

Initial Setting Mode

   

Set initial pattern: Set parameter

  to initial pattern in 

Operation Mode

Set initial step: Set parameter

  to initial step in

Operation Mode

 

Select edit pattern: Set parameter

  in 

Initial Setting Mode

  to set the pre-edit pattern, assume selection is ‘x’. 

Press

key  to  select  the  patterns  including  “SP‘x’0”,  ”tM‘x’0”,  ”SP‘x’1”,  ”tM‘x’1”… 

“SP‘x’F”,  ”tM‘x’F”,  ”PSY‘x’  ”,  ”CYC‘x’  ”,  ”LiN‘x’  ”,  where  ‘x’  is  the  selected  pattern,  which  can  be  0,  1,  …,  E, 
F. ”SP‘x’0”

  ”SP‘x’1”

…”SP‘x’F” are temperature settings of this step; ” tM‘x’0” 

” tM‘x’1”

  … ” tM‘x’F” are time

settings of this step; ”PSY‘x’ ” is the maximum effective procedure;    ”CYC‘x’ ” is the number of loops for executing
the loop, ”LiN‘x’” is the number of the subsequent patterns to be linked after executing this pattern.

Set initial slope: Set initial slope by parameter

  in 

Initial Setting Mode

(unit: 0.1

/min. or 0.1

/s) 

Set wait temperature: Set wait temperature by parameter

  in 

Initial Setting Mode

Set wait time: Unit min., set wait time by parameter

  in 

Initial Setting Mode

Set unit of program edit time: Set value corresponding to Y position of parameter

  in 

Initial Setting Mode

, e.g., 

xxYx (Y is 0 or 1; 0

/min., 1

/s)

Set SV display method on program mode: Set value corresponding to Y position of parameter

  in 

Initial Setting 

Mode

, e.g., Yxxx (Y is 0 or 1; 0

normal, 1

dynamic)

Set power off saving on program mode: Set value corresponding to  Y  position of parameter

  in 

Initial Setting 

Mode

, e.g., xxxY (Y is 0 or 1; 0

normal., 1

power off saving)

Note: When any settings or changes of the program parameters are made, please save the settings/changes to the
controller by opting for parameter SAVE. Otherwise, the settings/changes will be reset upon power-off.

How to 

SAVE:

Select

 in  the  menu,  then  press  the 

  keys  and  select 

 to  complete  saving.   The 

 key is displayed only when any settings/changes are made. 

Using RS485 communicatiion writing value 1 to address 1129H, the parameters will be saved.

Remote Mode: 

Input of setting value can be dynamic, an analog value (voltage or current) can be converted into a dynamic input

value. Two methods can be used for the conversion: positive slope or negative slope, they are depicted as follows:
a

  Positive slope Remote setting: Display of Remote analog input is in positive proportion with setting input, e.g.: Remote input

type is selected as 1~5 V analog voltage, Remote higher limit of input is set as 5000, Remote lower limit of input is 1000, 
decimal display is set as 0; when Remote input is 5V, the screen shows 5000; when Remote input is 2V, the screen show 
2000; this is the dynamic setting of the screen display. (Dynamic setting value =(Remote higher limit of input – Remote lower 
limit of input)*(Remote input value - lower limit of Remote input)/( higher limit of Remote input - lower limit of Remote input)+ 
Remote lower limit of input) 

b

  Negative Slope Remote setting: Display of Remote analog input is in negative proportion with setting input, e.g.: Remote 

input type is selected as 1~5 V analog voltage, Remote higher limit of input is set as 5000, Remote lower limit of input is 1000, 
decimal display is set as 0; when Remote input is 5V, the screen shows 1000; when Remote input is 2V, the screen show 
4000; this is the dynamic setting of the screen display. (Dynamic setting value =(Remote higher limit of input – Remote lower 

Содержание CND3 Series

Страница 1: ...CND3 Series Temperature Controller www omegamanual info Shop online at omega com For latest product manuals User sGuide e mail info omega com...

Страница 2: ...rves the right to alter specifications without notice U S A Headquarters Servicing North America Omega Engineering Inc Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Cana...

Страница 3: ...or connecting the thermocouple wires 6 Please use wires with resistance when extending or connecting a platinum resistance thermometer RTD 7 Please keep the wire as short as possible when wiring a pl...

Страница 4: ...Note Not all combinations may be available Check website under All Models to see list of available models...

Страница 5: ...perature 20 C 65 C Altitude Max 2000m Relative Humidity 35 80 RH non condensing Operation There are three modes of operation operation regulation and initial setting When power is applied controller g...

Страница 6: ...for the selection of Thermocouple or Platinum Resistance types PT TEMP UNIT Set temperature unit it wil not be displayed when in analog input mode TEMP HIGH Set up upper temperature limit the upper li...

Страница 7: ...will select P value accordingly 47 6 I Integral Time Setting display when Crtl PID FUZZY 2PID this parameter is set automatically when TUNE AT Set I value according to the selection of PID No n 0 5 Wh...

Страница 8: ...eters into the selected PID group Select the n th PID n 0 5 press to set 0 5 th PID parameters Set up the 0 th PID temperature value press Set up the 5 th PID temperature value press Set up the 0 th p...

Страница 9: ...to change the PV and SV display unit select decimal point and switch between F In Operation Mode SP 1 displays decimal place ex 25 5 degree SP 0 displays integral number ex 25 degree In Initial Settin...

Страница 10: ...put 4 20mA or linear voltage output 0 10V user s desire output value can be attained by using compensation function For example the analog output 1 can be adjusted in and parameters in Regulation Mode...

Страница 11: ...ent output L Linear voltage output S SSR output SV 3 rd digit indicates the function of accessory 2 N No function C CT measure E EVENT1 input R REMOTE input SV 4 th digit indicates the function of acc...

Страница 12: ...e Some of the terms are explained as follows a Initial pattern set the program to start running at a sequential number of patterns b Initial Step set the program to start running at a sequential numbe...

Страница 13: ...Y position of parameter in Initial Setting Mode e g xxxY Y is 0 or 1 0 normal 1 power off saving Note When any settings or changes of the program parameters are made please save the settings changes t...

Страница 14: ...adjustment by parameter in Regulation Mode Remote lower limit Setting Remote lower limit by parameter in Regulation Mode Remote higher limit Setting Remote higher limit by parameter in Regulation Mode...

Страница 15: ...Initial Setting Mode To set for heating or cooling control Select desired output control by parameter in Initial Setting Mode If no board is inserted in Output2 selection items are H1 C1 H for heating...

Страница 16: ...and the AT LED in the panel goes out The calculated PID parameters are displayed in and of which their content can be revised by the user Automatic switching over Multiple PID sets Set parameter to 0...

Страница 17: ...g Set a value corresponding to Y position by parameter in Initial Setting Mode such as xxYx Y can be 0 or 1 0 30A 1 100A CT2 100A setting Set a value corresponding to Y position by parameter in Initia...

Страница 18: ...on F1 F2 button can be used to switch between PID and MANUAL control mode ALRS Selecting this function F1 F2 button can be used to reset Alarm Hold status SV2 Selecting this function F1 F2 button can...

Страница 19: ...will return to PV SV display mode 3 Enter the new password two times in the screen The screen will return to PV SV display mode with the keys unlocked If the two entries of password are not the same...

Страница 20: ...if PV value is lower than the setting value SV AL H This alarm output is OFF when PV value is higher than the setting value SV AL L ON OFF SV AL H SV AL L SV 9 Disconnection Alarm This alarm output op...

Страница 21: ...PV Measuring unit is 0 1 updated one time in 0 1 second The following reading value display indicates error occurs 8002H Initial process Temperature value is not got yet 8003H Temperature sensor is n...

Страница 22: ...r 0 15 1032H Remaining time of the executed step second Only read 1033H Remaining time of the executed step minute Only read 1034H No of currently executed step Only read 1035H No of currently execute...

Страница 23: ...Linear Output 2 Adjust current 1scale 1 A Adjust voltage 1scale 1mV 1119H Adjust Lower Limit of Analog Linear Output 2 Adjust current 1scale 1 A Adjust voltage 1scale 1mV 111AH Adjust Retransmission...

Страница 24: ...Starting data address 10H 08H Starting data address 10H 08H 00H 10H 01H 10H 01H 10H Number of data word Bit 00H 00H Start address data 1000H 081xH 01H 17H Data content 03H FFH Data content 03H FFH 02H...