Manual Tuning
Tune the controller if any of the following occurs:
•
The controller is installed in a new system
•
The controller is used as a replacement in an existing system
•
The input sensor is relocated or changed
•
The output device is relocated or changed
•
The setpoint is significantly changed
•
Any other condition that will alter the dynamics of the system
Proportional Band
The proportional band is a band around the setpoint of the CN4431
where the output is between 0% and 100%. The percentage of output is
proportional to the amount of error between the setpoint variable (SV)
and the process variable (PV). Outside of the proportional band the out-
put is either 0% or 100%
The proportional band on CN4321/CN4431 is equidistant from the main
setpoint as illustrated below.