51
1-5/0-5V DC or 4-20/0-20mA DC signal, integers, tenths or
hundredths of a unit may be entered depending on the
programmed input range.
Setting:
0 -None
1- Tenths of a unit
2 - Hundredths of a unit
P-AH
Alarm Type 1:
P-AL
Alarm Type 2:
These functions set the control action
for the optional alarm output relays. They can be pro-
grammed for absolute, deviation, combination, or zone
alarm configuration. The high and low alarm setpoints
are set with primary menu parameters AH and AL (AL is
not applicable in the case of CN4321). The absolute
alarm configurations are independent of main setpoint.
The alarm output relays are energized when the
process variable exceeds the alarm setpoint, an
absolute value. The deviation alarm configuration is
main setpoint tracking. The alarm output relays are
energized when the process variable exceeds the main
setpoint by a deviation value set by AL or AH. The com-
bination alarm
configurations are a mixture of both the deviation and
absolute value settings for the high and low alarms.
With zone alarm configurations the alarm output is
energized between the range set by AL and AH.
One of the alarm types is Alarm with Hold. In this case
the alarm is not turned on the first time the measured
value is in the alarm band. Instead it turns on only when
the measured value goes out of the band and enters it
again. This type is useful when using deviation alarm
with step type input.
Содержание CN4321
Страница 33: ...32 SYSTEM WIRING DIAGRAMS Example 1 Example 2...
Страница 45: ...44 Deadband Overlap...
Страница 48: ...47 Table of Input Type Codes...
Страница 50: ...49...
Страница 53: ...52 Table of Alarm Action Type Codes CN4321...
Страница 54: ...53 Table of Alarm Action Type Codes CN4431...
Страница 59: ...58 Table of Output Type Codes...