45
powerful cooling loads. Enter a value based on the
power of your cooling load.
Setting Range: 0.0 to 100.0
Not indicated without control output #2 option.
Set to “0” for On/Off control.
db
Deadband/Overlap:
The Deadband/Overlap is that per-
centage of the heating side of the proportional band
where the heating (output #1) and the cooling (output #2)
outputs are separated by a deadband or where they
overlap on a heat/cool controller. A value greater than
zero establishes a Deadband area where neither the
heating nor cooling outputs are energized, for more pow-
erful heating and cooling loads. A value less than zero
establishes an Overlap area where both the heating and
cooling outputs are energized at the same time, for less
powerful heating and cooling loads. Enter a value based
on the power of your heating and cooling loads as well
as the application’s efficiency in maintaining tight