22
9.3. Installation procedure
•
The RDP refrigeration air dryer is typically delivered on the standard pallet on which it is
screwed with four screws.
•
The RDP refrigeration air dryer can be lifted with forklift trucks.
•
Remove the screws and the pallet before positioning the dryer at the desired location.
•
The refrigeration air dryer should be installed in such a way that it is protected from weather
(for example, a compressor station).
•
It is recommended to have 1 m of space around the dryer. This measure facilitates
maintenance.
•
Make sure that the dryer is protected against vibration and mechanical wear.
•
The dryer must stand firmly on a horizontal basis. The tilt of the unit must not exceed ± 3 °.
The best way to achieve these conditions is to fasten the dryer with screws onto a horizontal
base through the appropriate openings on the base. If the dryer is not installed properly, there
may be improper operation. Fastening the dryer with screws is not obligatory.
•
RDP 20 - 235 drier models can be attached to
the wall with wall screws - the position of the
holes in the illustration is shown. (maximum
size M8)
•
The pipe connections for the compressed air
in the front and back of the dryer must be
fitted with suitable valves that allow the
independent installation or removal of the
dryer from the system.
•
Install a super fine coalescent filter on the
input side and pre-filter on the output side. It
only applies if the dryer has no built-in filters.
•
Check that the air is properly treated before
the dryer (air conveyor, cyclone separator,
filters, condensate separators ...).
•
Remove the plastic covers from the dryer's
input and output.
•
Connect the air source to the dryer.
•
The temperature and flow of the intake air
into the refrigeration air dryer must remain
within the limit values indicated on the
nominal label of the device.
•
The pipelines of the system must be free of dust, rust, filings and other impurities and must
correspond to the flow of the dryer.
•
It is also recommended that you arrange an air bypass line.
•
Connect the dryer to the power source. Ensure that the supply voltage and the frequency
correspond to the data on the type label (± 5% acceptable tolerance for the supply voltage).
•
Remove the packaging and other material that could hinder the dryer during normal
operation.
Содержание RDP Series
Страница 28: ...28 16 Maintenance notebooks MAINTENANCE TYPE DATE SIGNATURE NOTES First installation...
Страница 29: ...29...
Страница 30: ...30 17 Drawings of RDP refrigeration air dryers RDP 20 100...
Страница 31: ...31 RDP 140 235...
Страница 32: ...32 RDP 300 480...
Страница 33: ...33 RDP 600 950...
Страница 34: ...34 RDP 1150 1900...
Страница 35: ...35 RDP 2600...
Страница 36: ...36 16 Electro schemes of RDP refrigeration air dryer RDP 20 180...
Страница 37: ...37 RDP 235 600...
Страница 38: ...38 RDP 750 1900...
Страница 39: ...39 RDP 2600...