17
Troubleshooting
errors
Troubleshooting and maintenance procedures can only be performed by qualified personnel with
the necessary knowledge.
Before any maintenance or service parts make sure that:
- no part or device is powered and must not be connected to a power source
- that no part or device is under pressure and must not be connected to a compressed air
system under pressure,
- that the maintenance staff fully and accurately read the operating instructions, and in
particular the chapters relating to safety at work.
SYMPTOM
POSSIBLE CAUSE - PROPOSED ACTIVITY
None of the LEDs lights are
on
● Make sure that the system is connected to a power source.
● Check the electrical
installation (internal and external).
● Check that the circuit board is not damaged.
...................................................................................................................
...................................
...................................................................................................................
................. ..
The TEST button is
pressed, but
the condensate is not
drained
● The service valve in front of the drain is closed
- open it.
● The dryer
is not pressurized - set normal operating conditions.
● The solenoid valve is defective
- replace the condensate separator.
● The circuit board is damaged
- replace the condensate drain.
Condensate is only
drained when
the TEST button is
pressed.
● The capacitive sensor is dirty
- open the condensate separator and
clean the plastic tube of the sensor.
...................................................................................................................
...................................
...................................................................................................................
................. .. ............
...................................................................................................................
...................................
...................................................................................................................
..... ..
The spout blows out air.
● The electromagnetic valve diaphragm is dirty
- open the drain and
clean it.
● The capacitive sensor is dirty
- open the condensate separator and
clean the plastic tube of the sensor.
The drain is in a state of
alarm.
● The capacitive sensor is dirty
- open the condensate separator and
clean the plastic tube of the sensor.
● The service valve in front of the drain is closed
- open it.
● The dryer is not pressurized
- set normal operating conditions.
● The solenoid valve is defective
- replace the condensate separator.
NOTE: When the condensate drain is in alarm condition, the solenoid valve will open every 7
minutes for 7.5 seconds.
Содержание RDP Series
Страница 28: ...28 16 Maintenance notebooks MAINTENANCE TYPE DATE SIGNATURE NOTES First installation...
Страница 29: ...29...
Страница 30: ...30 17 Drawings of RDP refrigeration air dryers RDP 20 100...
Страница 31: ...31 RDP 140 235...
Страница 32: ...32 RDP 300 480...
Страница 33: ...33 RDP 600 950...
Страница 34: ...34 RDP 1150 1900...
Страница 35: ...35 RDP 2600...
Страница 36: ...36 16 Electro schemes of RDP refrigeration air dryer RDP 20 180...
Страница 37: ...37 RDP 235 600...
Страница 38: ...38 RDP 750 1900...
Страница 39: ...39 RDP 2600...