background image

CDi-16B - Installation and operating manual 

www.omega-air.si 

 

Components 

 

 

 

 

 

Part 

 

Part 

 

Part 

 

Part 

Housing 

11  Spring base 

21  Sensor 

31  O-ring 

  

 12,0x2,0 

Cover 

12  O-ring 

  

 17x2,0 

22  Cable leader 

32  O-ring 

  

 10,0x2,0 

Valve seat 

13  Valve inlet connector 

23  Connection 1/8”-

 

8/6 

33  O-ring 

  

 21,95x1,78 

Damper 

14  Screw plug 1/2” 

24  Screw PT KA 35x16 

34  Screw KA 30x8 

Valve housing 

15  Connection Al 

 

50 

25  Foil keyboard 

35  Screw KA 30x8 

Plunger 

16  Fixing screw 1/8” 

26  O-ring 

  

 38,0x3,0 

36  High voltage label 

Spring 

17  Probe holder  

27  Electronic 

37  Screw KA 30x6 

Coil 

18  Probe holder cover 

28  O-ring 

  

 7,0x2,0 

38  Flat seal 

 

10x1 

O-ring

  

5,8x1,5  19  Probe housing 

29  O-ring 

  

 9,0x1,5 

39  Contact spring 

 

2x10 

10  Plunger sealing 

20  Electronic 

30  Data label 

40  Sealing 

Содержание CDi-16B

Страница 1: ...tion and operating manual CDi 16B Please read the following instructions carefully before installing electronic drain unit into service Trouble free and safe operating of the unit can only be guarante...

Страница 2: ...ng 21 95x1 78 4 Damper 14 Screw plug 1 2 24 Screw PT KA 35x16 34 Screw KA 30x8 5 Valve housing 15 Connection Al 50 25 Foil keyboard 35 Screw KA 30x8 6 Plunger 16 Fixing screw 1 8 26 O ring 38 0x3 0 36...

Страница 3: ...5 C 35 to 149 F Upper Inlet connection G 1 2 BSP Lower Inlet connection G 1 2 BSP Outlet connection G 1 8 BSP Power interface 3 x 0 5mm 2 Protection class IP65 Volume 0 1 l Mass 0 96 kg Dimensions A x...

Страница 4: ...abel Do not use the device in hazardous areas with potentially explosive atmospheres Use original spare parts only Use the device for the appropriate purpose only Appropriate use CDi 16B series electr...

Страница 5: ...gnal to electronic board Electromagnetic valve 4 is than opened to discharge accumulated condensate through outlet connection 5 When reservoir 2 has been emptied the valve 4 closes back without any lo...

Страница 6: ...commended Install ball valves 2 only Recommended connection 4 to water oil separator 1 2 The inclination of the unit must not exceed 5 in both axes If device is not installed correctly it could cause...

Страница 7: ...ped air prevents the condensate being purged from drain 5 During installation ensure that no water pockets are formed in the piping 6 7 8 When drainage is to take place directly from a pipeline it is...

Страница 8: ...11 Warning Upper and back connections cannot be used as condensate inlet at the same time 13 14 STANDARD INSTALLATION Upper connection Inlet Back connection Closed VENTING LINE INSTALLATION Upper con...

Страница 9: ...ctions LED indicator TEST button LED indicator LED indicates device condition 1 Green ON Power on reservoir empty waiting condensate to accumulate 2 Green FLASHES Device is discharging condensate 3 Re...

Страница 10: ...osed for one second This cycle repeats for five minutes up to 100 discharges In case the reservoir empties during overload mode device enters normal mode again ALARM If drain was still not able to dis...

Страница 11: ...nce work take the drain out of operation switch off the power supply and depressurize the unit Service kits Based on type of CDi 16B drain following servis kits can be used SERVIS KIT CDI 16 B 230V SE...

Страница 12: ...lisation passed by After connection wait 2 sec for system initialisation Check for voltage in circuit Check the cable and power connection Connect CDi 16B to proper voltage Mistake must be repaired by...

Отзывы: