CDi-16B - Installation and operating manual
www.omega-air.si
10
Operating modes
NORMAL
When sensor detects condensate the valve opens up to one second to discharge. Maximum
number of discharges in normal mode is up to 20.
OVERLOAD
If sensor detects condensed water continuously for 100 seconds, drain enters overload
mode. In this mode, the valve is opened for two seconds and closed for one second. This
cycle repeats for five minutes (up to 100 discharges). In case the reservoir empties during
overload mode, device enters normal mode again.
ALARM
If drain was still not able to discharge all condensate it enters alarm mode. In this mode, the
valve is opened for three seconds every fifty seconds. In case the reservoir empties during
alarm mode, drain enters normal mode again.
Alarm output
The switch is closed when CDi operates normally and it is open when CDi is in alarm mode or
when power is disconnected.
ALARM
OFF
U
max
= 200 Vdc
I
max
= 0,5 A
Output
Output