D877 MGB Rev01 HE250.docx 

The uphill reference speed are however limited, during operation, to the  value corresponding to the nominal 
capacity of the pump set in Par.102, increased by a percentage set in Par. 233. 
So to ensure to arrive at the maximum flow rate to the piston, you must set the Par. 233 to a value that 
compensates for the variability of the pump, and which enables however not exceed the legal limit of 
increase of the nominal speed. 
It must then set the speed parameter provided with a value equal to or greater than the limit reference speed. 
It is generally sufficient to increase the speed prescribed value, the percentage set in Par.233. 
The value of the limit reference speed (VRL) uphill, you can still calculate as follows: 
VRL = P102 x (P233 / 100 + 1) / (P101) ^2 x P103 / P104 x P109 x 21.22 
The system can then work to always make the most of the flow supplied by the pump and direct it to the piston, 
blocking  the  control  when  the  VSC  valve  reaches  a  considered  closing  position.  During  operation  in  this 
position on the DSP display u6. 
In the deceleration position the system acquires the current speed and the control returns to act to calculate 
the deceleration necessary to obtain the deceleration distance set in the parameters. 
Note: 
To reduce the consumption and ensure the functionality of the system, set the low-speed value and of the stop 
space so as to limit the stopping time to 1-1.5 s max, according to the following formula: 
Time [s] = 2 x Stop space [m] / Low-speed [m/s] 
es.: 

2 x 0.02 [m] / 0.05 [m/s] = 0.8 s 

6.3 

With VVVF drive working valve unit HEVOS HE250 

The valve unit Hevos 250 can work in conjunction with a VVVF drive, dedicated for the hydraulics systems, 
which works upward for adjust the speed of equipment, by setting the parameter P231 = 1. 
In this condition the valve unit remains passive throughout the upstroke and the flow coming from the pump is, 
at all times, addressed to the piston. 
The substantial differences compared to normal operation concerned solely with the up phase and they are: 

1. 

In the upward the single input recognized by the board is UP 

2. 

The test command relief valve is not executed 

3. 

The upward UCM test command is not executed 

4. 

During the upstroke the PNP1 monitoring signal is not operated and remains at level 0 

5. 

The output contact AVV (motor-pump management) is activated for to manage the motor stopping 

6. 

During the upstroke is not used the ERS solenoid 

 

 
 
 
AVV 

Motor activation contact from 

SCH001 board to control panel 
UP 

Upward  signal  to  SCH001 

board and to VVVF drive input 

High  Speed  signal  to  VVVF 

drive input 

Inspection  signal  to  VVVF 

drive input 
MOT 

Motor-pump  power  supply 

managed  by  the  VVVF  drive  and 
controlled by the upstroke contactors 
PI 

Parameters  generally  set  on 

VVVF  drive  (see  specific  VVVF 
manual) 
Note:  During  the  upstroke  travel  the 
Display of SCH001 shows "ir". 
 

 

Содержание HEVOS HE250

Страница 1: ...D877 MGB Rev01 HE250 docx 1 50 OPERATING INSTRUCTIONS FOR HEVOS HE250 VALVE...

Страница 2: ...N 00 23 10 2019 Emission 01 26 11 2019 11 Remarks added to electric wiring scheme 01 26 11 2019 12 Updated App reference for WiFi connection 01 26 11 2019 16 24 Updated figure and commands description...

Страница 3: ...xing 17 2 15 Upward working cycle 18 2 16 Downward working cycle 20 2 17 Releveling 21 2 18 Rapture valve test DSP FC FP 21 2 19 Maximum pressure valve test DSP PP HP 22 2 20 Error condition 22 2 21 U...

Страница 4: ...and codes HEVOS HE250 valve unit 31 5 1 Parameters 31 5 2 Errors 36 6 Automatic reduction of travel times 39 6 1 Recovery leveling space 39 6 2 Reduction of starting time and maximum upward speed 39...

Страница 5: ...allation use and maintenance personnel The herewith instructions aim to permit the positive and safe execution of the installation operations starting up working control maintenance and possible repai...

Страница 6: ...ssary accessories and or required also check the correspondence of data on delivery and identification plates with those of the expected material 1 3 Storage In the installation waiting the group must...

Страница 7: ...nimum pressure clockwise increase anticlockwise decrease 26 Hand pump 27 Hand pump maximum pressure valve clockwise increase anticlockwise decrease 28 Hand pump non return valve 29 Hand pump air relea...

Страница 8: ...se increase anticlockwise decrease 26 Hand pump 27 Hand pump maximum pressure valve clockwise increase anticlockwise decrease 28 Hand pump non return valve 29 Hand pump air release screw 97 VNR valve...

Страница 9: ...27 Hand pump maximum pressure valve clockwise increase anticlockwise decrease 28 Hand pump non return valve 29 Hand pump air release screw 97 VNR valve block control throttle TF Flow meter TP1 Pressur...

Страница 10: ...10 50 D877 MGB Rev01 HE250 docx Plate mounting hole shape pattern Pump tube mounting hole pattern Weight 13kg Measures in mm...

Страница 11: ...operating LD31 LED Green ON Normal condition LD32 LED Blue ON Wi Fi module activated LD35 LED Orange ON SD memory activated OPTO ISOLATED DIGITAL INPUT Working voltage 20 60 VDC 100 mA CN6 UP Upward...

Страница 12: ...covery To save the parameters via SD CARD must use a Micro SD 2 to 16 GB already formatted FAT 32 Switch the RSW selector in position 7 the display will then show oc and will turn on ON Yellow LED LD3...

Страница 13: ...nt condition The second is to acquire the overload value with empty cabin In this case the P111 parameter must contain the value of the nominal laod rate and therefore will be entered in parameter P10...

Страница 14: ...deceleration change rate P312 Downward low speed m s fpm P313 Downward stopping distance m P314 Downward releveling acceleration distance m ft P315 Downward releveling speed m s fpm P316 Downward rel...

Страница 15: ...ver during operation the reference speeds in upward are limited to the value corresponding to the nominal pump flow rate set in P102 plus the percentage value set in P233 Downward starting conbination...

Страница 16: ...VALVE UNBLOCK SOLENOID VALVE ZERO VSC VALVE POSITION SENSOR TF FLOW SENSOR TP1 PRESSURE SENSOR TT TEMPERATURE SENSOR MPP VSC VALVE COMAMNDS TEPPER MOTOR D MPP STEPPER MOTOR CONTROL DRIVER RM STEPPER M...

Страница 17: ...D877 MGB Rev01 HE250 docx 17 50 2 14 SCH100 board dimensions and fixing Min space for SD and USB used N 7 Metallic spacers Board fixing Metal plate 1 5 mm for DIN 35 bracket...

Страница 18: ...tank at low pressure to allow a proper motor starting and avoid hit in the cabin caused by pump direct flow to piston UPWARD 4 8 MOTOR STARTING COMPLETED AND CABIN ACCELERATION DSP u1 Once finisch the...

Страница 19: ...esidual distance setted in the P458 parameter The calculation is reset when the board is off UPWARD 8 8 STOPPING DSP u5 Upon arrival at the stopping contact in the shaft it must turn off the upward UP...

Страница 20: ...speed signal P304 oppure P305 P306 P317 DOWNWARD 5 7 DECELERATION DSP d3 Upon arrival at the deceleration contact in the shaft turn off the high speed HSP signal or the SP3 signal if the parameter P4...

Страница 21: ...peed and the stopping distance 2 18 Rapture valve test DSP FC FP Block the system to exclude the possibility of travel Set the working selector RSW 3 DSP FC and then press S1 button until appear FP on...

Страница 22: ...Y if not performing a new maximim pressure test by pressing the button S1 as described above or a normal maneuver setting the selector RSW 0 Note As an alternative to the use of RSW switch you can act...

Страница 23: ...IAGRAM SCH001 Output ON Device Command ON M Motor input ENR ENR Solenoid valve input ERS ERS Solenoid valve input 2 UPWARD WORKING CYCLE DIAGRAM Motor Starting SCH001 Input ON b Upward deceleration co...

Страница 24: ...rs open it must activate the stop element interrupting any signal and command to the valve group In particular must be disconnected on SCH001 electronic card the inputs of ENR solenoid valves and ERS...

Страница 25: ...bin The device must operate the stop element i e interrupt signals to the valve group during the descent before the cab moves away from 200 mm from the floor In particular to activate the stop element...

Страница 26: ...el waiting for commands 2 4 ACTIVATION VALVE ENR DSP A1 Power input of only solenoid valve ENR The electronic board detects the necessary conditions and activates the output solenoid ENR which control...

Страница 27: ...azionare il dispositivo di emergenza manuale sino all intervento del ripescaggio If at the end of the relevelling the control panel repeats the test with the solenoid activation ERS DSP A3 cause as pr...

Страница 28: ...block of the the signal allows to check error detection from the electrical control panel Only with the parameter P461 0 the PNP1 signal switches according to the normal operation It is possible to c...

Страница 29: ...il tipo modello e i dati di certificazione oltre ad un QR code The valve group is applied a plaque showing the name and address of Manufacturer serial number the type model and the certification data...

Страница 30: ...t again At the end remember to close the gauge cut tap 4 2 Upward movement of the cab The displacement of the cabin upwards is possible by acting on the hand pump 26 through the appropriate actuating...

Страница 31: ...rd 0000000 9999999 0000000 8369111 Parameter Nr Desc Hand term Large Description Unit Setting Range Default Value Note P2 Upwars Par UPWARD PARAMETERS Min Max 201 AccStart U Upward initial acceleratio...

Страница 32: ...t D Downward stopping distance m 0 000 10 000 0 010 314 Acc Dist DR Downward releveling acceleration distance m 0 000 10 000 0 010 315 RelevSpeedD Downward releveling speed m s 0 000 0 300 0 050 P304...

Страница 33: ...pressure 0 s 1000 0 20000 3000 451 ControlType Control type 1 PID PID Map 0 Map 0 2 1 452 SP Calcul Deceleration space recalculation 1 Activate 0 1 0 453 SignalSpeeD Downward high speed signal 1 Acti...

Страница 34: ...and input 0 1 524 OnOffI MAN Maintenance command input 0 1 525 OnOffI DHS Downward high speed optional command input 0 1 526 OnOffI PWM Motop pump started input 0 1 527 OnOffI HS1 Auxiliary speed 1 co...

Страница 35: ...on 0 9999 712 Copy Master Master parameters duplication in the slave nodes 0 9999 713 Reset Err Errors reset master slave 0 9999 P8 Technic Par TECHNICAL PARAMETERS Min Max 851 Gain U4 Upward gain U4...

Страница 36: ...as follow EA Warning error not blocking the maneuver the relay ERR does not turn on and the error message disappears at the first maneuver Er Generic error blocking the maneuver Er Generic error bloc...

Страница 37: ...movement flow meter error Check if there are impediments to the flow 17 Er At the working anomaly of a solenoid valve Check starting input voltage ERS and ERN solenoid valves 18 Er At rest VSC zero s...

Страница 38: ...roblem 43 Er Stepper temperature warning MPP driver temperature attention level 44 Er Stepper overtemperature MPP driver thermal protection for valve ERS problem 45 Not used 46 Not used 47 Er CAN erro...

Страница 39: ...me and maximum upward speed The reduction of the total upstroke time reduces the consumption and oil heating The synchronization between the output contact AVV and digital input SFY electronic card al...

Страница 40: ...em set the low speed value and of the stop space so as to limit the stopping time to 1 1 5 s max according to the following formula Time s 2 x Stop space m Low speed m s es 2 x 0 02 m 0 05 m s 0 8 s 6...

Страница 41: ...er shut off valve 2 Release all pressure by manually adjusting the knob 17 Check that the level of pressure on the pressure gauge is next to zero equal to the valve setting 25 then after one minute re...

Страница 42: ...r plate is in the correct position and legible Also check the instructions of the emergency maneuvers the oil plate the wiring diagrams of the picture and the hydraulic diagram of the control unit 7 3...

Страница 43: ...cific stop contacts when micro leveling stopping To connect the auxiliary group contact the Technical Office UP Upward signal SCH001 board ML Micro leveling pump motor power supply PI Dependent speed...

Страница 44: ...address of the CAN node 1 to 127 of the corresponding card P 477 defines the total number of Slaves in the Multi specific valves system 1 to 7 P 478 defines the active status 1 or inactive 0 of the co...

Страница 45: ...crease 26 Hand pump 27 Hand pump maximum pressure valve clockwise increase anticlockwise decrease 28 Hand pump non return valve 29 Hand pump air release screw 97 VNR valve block control throttle TF Fl...

Страница 46: ...d in both terminator cards while it is to be let free in those intermediatedie The connections to the devices valve groups and the power of the board are the same as those of the single group Is possi...

Страница 47: ...E SENSOR MPP VSC VALVE COMAMND STEPPER MOTOR D MPP STEPPER MOTOR CONTROL DRIVER RM STEPPER MOTOR CONNECTION RELAY CN1 5 BOARD SENSOR INPUT CONNECTIONS CN6 8 BOARD SIGNALS INPUT CONNECTIONS CN9 16BOARD...

Страница 48: ...48 50 D877 MGB Rev01 HE250 docx 9 EU type certificate example...

Страница 49: ...D877 MGB Rev01 HE250 docx 49 50...

Страница 50: ...50 50 D877 MGB Rev01 HE250 docx OMARLIFT s r l Via F lli Kennedy 22 D 24060 Bagnatica BG ITALY Phone 39 035 689611 Fax 39 035 689671 Email info omarlift eu Web http www omarlift eu...

Отзывы: