30
C0
0
99
Second
x10
0
The minimum time required for the
ignition to activate after the device
is energized.
C1
0
99
Minute
5
Minimum time required for
compressor to start 2 consecutive
starts
C2
0
99
Minute
3
The minimum time that the contact
must remain closed between the 2
contact activation times
C4
0
100
%
50
Percentage of the compressor
running time during cabin sensor
fault (P1 alarm)
PARAM.
MINIMUM
MAXIMUM
UNIT
FACTORY
SETTINGS
DEFROST
d0
0
99
Hour
8
How many hours to defrost
0 = defrost is never activated
d3
0
99
Dakika
30
How long will the defrost take?
PARAM.
MINIMUM
MAXIMUM
UNIT
FACTORY
SETTINGS
ALARMS
A1
-99
99
°C / °F(1)
-99
Low-temperature alarm value or
difference value depending on the
set value (If A5 is negative; A1 is
the solid value, if positive, the set
value is the dependent differential
value)
A4
-99
99
°C / °F
99
For the high-temperature alarm,
the difference must be lower than
the set value (If A5 is negative; A4
is the solid value, if positive, the
set point is the connected
differential value.)
A5
-99
99
°C / °F
-2
Reset differential for parameters
A1 and A4
A7
0
99
Minute
x10
2
Delay for activation of temperature
alarm
Note: Temperature alarms are
disabled for 1 hour after the end of
the defrost.
PARAM.
MINIMUM
MAXIMUM
UNIT
FACTORY
SETTINGS
DIGITAL INPUT
i0
0
1
----
0
Stopping the compressor by
triggering the door switch input
0 = No 1 = Yes
i1
0
1
----
0
Type of door switch input
0 = normally closed
1 = normally open
i2
-1
99
Minute
30
Delay time “id” alarm code for the
door open alarm
-1 = the door open alarm never
goes off
PARAM.
MINIMUM
MAXIMUM
UNIT
FACTORY
SETTINGS
OTHER
NS
0
99
X10000
0
The compressor starts limit for