Figure 1
Diffusor
Reflector
Plastic base
Figure 2
Figure 3
Non-maintained
operation
Maintained
operation
NOTE:
LED=
Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained
(*)
A: Including test device
90: 1.5 hour duration
180: 3 hour duration
(*)
Maintained operation: The luminaire lights its
illumination source, when it is powered by the
mains power supply or not
.
Non-Maintained operation: The luminaire lights its
illumination source,
only in power supply’s
failure.
Battery replacement
.
It can be done only by a competent person and after the mains interruption
.
1.
Dismantle the device
(step 1 of
the installation
instructions)
.
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step
4
of the installation
instructions
) and place it in
the position of the old one.
4. Follow the step
6
of the installation procedure and power the device.
Installation instructions
1.
To instal the device you have to dismantle carefully the device with a flat screwdriver as shown in
figure 1.
2.
Pass the mains cables thru the hole (point 1 in figure 2).
The luminaire must be connected to a
permanent electrical installation
to ensure
the
immobilization of the cable.
3.
Mount the base plastic on the wall by using the included mounting accessories in points 2 and 3 in
figure 2.
4.
Connect the battery`s cable with the appropriate terminal (figure 3).
5.
Connect the mains cables to the terminal block as shown in figure 4.
6.
Refit with care the removed plastic parts and power on the luminaire.
NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for battery
charging to perform the named autonomy.
4
1
2
3
Figure 4
For fuse ratings
see text