background image

923378

005

_23_001

Page 2 from

 

2

Figure 1

Diffusor

Reflector

Plastic base

Figure 2

Figure 3

Non-maintained

operation

Maintained

operation

NOTE: 

LED=

 

Light Emitting Diode

LABELING EXPLANATION:
X: Self contained
1: Maintained

 (*)

A: Including test device
90: 1.5 hour duration 
180: 3 hour duration 

(*) 

Maintained operation: The luminaire lights its 

illumination source, when it is powered by the 
mains power supply or not

Non-Maintained operation: The luminaire lights its 
illumination source,

 

only in  power supply’s 

failure. 

Battery replacement

It can be done only by a competent person and after the mains interruption

.

1. 

Dismantle the device

 

(step 1 of

 the installation 

instructions)

.

2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step 

4

 of the installation 

instructions

) and place it in

    the position of the old one.
4. Follow the step 

6

 of the installation procedure and power the device. 

Installation instructions

1. 

To instal the device you have to dismantle carefully the device with a flat screwdriver as shown in 

    figure 1.

2. 

Pass the mains cables thru the hole (point 1 in figure 2).

 

The luminaire must be connected to a

    permanent electrical installation

 to ensure

 the 

immobilization of the cable.

3. 

Mount the base plastic on the wall by using the included mounting accessories in points 2 and 3 in 

    figure 2.

4. 

Connect the battery`s cable with the appropriate terminal (figure 3).

5. 

Connect the mains cables to the terminal block as shown in figure 4.

6. 

Refit with care the removed plastic parts and power on the luminaire.

NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for battery 
charging to perform the named autonomy. 