Date 

22/4/2021 

Document number 

921100400_09_005 

Page 

46 of 71 

 

 

46 / 71 

5.1.4 

Device LED Address 

DEVICE LED ADDRESS

” 

option starts a countdown procedure of 25 

minutes  while  every  connected  fire  detection  device  indicates  its 
address by a special flashing pattern that is repeating. 

-

 

3burst short flash 

-

 

2 seconds gap 

-

 

number of flashes multiplied by tens (with 1s gap between) 

-

 

5 seconds gap 

-

 

2burst short flash =>2s gap 

-

 

number of flashes multiplied by ones (with 1s gap between) 

-

 

5 seconds gap 

-

 

repeat 

The  address  of  the  observed  point  is  calculated  by  adding  tens  and 
ones.  For  example,  address  #

124

  will  be  indicated  with  the  following 

pattern: 

 

Figure5-7.Device led address

 

 

Figure5-8.Device led address pattern example of #124

 

 

5.2 

Check Menu 

This submenu is insisted of a set of inspection functions, used for system inspection, after initial installation 
or troubleshooting. 

5.2.1 

Check points 

The first option “

POINTS

” displays the screen on the right, used to 

check communication quality between the control panel and a point 
(addressable  device).  Use  up/down  keys  to  navigate  between 
addresses and left/right keys to navigate between loops. 

The first section contains point’s information, first line displays points 

address  (1.001  equals  to  loop  1,  point  address  1),  second  line 

displays  point’s  name  and  third  line  indicates  point  type  (e.g.  call 

point). 

The next section contains point’s communication data. “

VALUE

” field 

indicates  the  point’s  current  reading  value  (fire  detection),  “

VALID 

PACKETS

”  indicate  the  sum  of  the  correct  communication  data 

packets received and “

INVALID PACKETS

” indicate the sum of the 

wrong  data  packets  received.  On  normal  conditions,  only  “

VALID

 

PACKETS

” counter should increase.

 

 

Figure5-9.Check point 1

 

 

Содержание BSR-1000

Страница 1: ...BSR 1000 BSR 1001 BSR 1002 BSR 1004 Analogue Addressable Fire Alarm Panel 1 2 and 4 loops Installation Programming Operation WARNING READ THIS MANUAL PRIOR TO ANY INSTALLATION OR USE...

Страница 2: ...Test LED 13 2 7 3 Information 14 3 User s Menu 19 3 1 Enable Disable segments 21 3 2 Delays Menu 22 3 3 Set Date Time 22 3 4 Backlight mode 23 3 5 Change user s code 23 3 6 PC Communication 24 3 7 Ope...

Страница 3: ...ction 49 5 3 3 Autoaddressing points 50 5 3 4 Change point address 51 5 3 5 General resound 51 5 3 6 Conventional sirens 51 5 3 7 AUX Relay 52 5 3 8 Extra Relays 52 5 3 9 Panel Network 53 5 3 10 Loops...

Страница 4: ...lation 66 7 3 Battery Calculation 67 8 BSR 1000 Repeater panel 67 8 1 General 67 8 2 Functions 68 8 3 Installation 68 8 4 Wiring 68 8 5 Setup repeater network 68 8 5 1 Setup repeater address 68 8 5 2...

Страница 5: ...tion according to your installation size All features and indications are in accordance with European standards 54 2 and 54 4 The BSR 100X series Analogue Addressable Fire Alarm Panels is ideal for me...

Страница 6: ...rmation regarding the fire detection system state The LED indicators provide general information e g if there is any alarm the General Alarm LEDs are lit while more detailed information is displayed o...

Страница 7: ...rm outputs BUZZER SILENCE Mutes unmutes audible buzzer LAMP TEST Turns on all LED indicators for 5 seconds to visually inspect for functionality OVERRIDE DELAYS Immediately activates all alarm outputs...

Страница 8: ...emporarily deactivated during alarm state POWER green Mains power connection indication steady lit ok blinking power down PREALARM yellow Prealarm detected TEST yellow The system or part of it is unde...

Страница 9: ...s of the control panel according to the description and are yellow Figure1 4 LED Indicators below the screen GENERAL FAULT General panel fault SYSTEM FAULT System fault hardware SUPPLY FAULT Power fai...

Страница 10: ...lowing information appears when available alternating every 3 seconds The control panel address and the name of it when panel network is enabled The number of the segments under test if any The number...

Страница 11: ...e buzzer until a new event appears Pressing SIREN SILENCE key will deactivate all sirens as long as all other output relays that are set to behave respectively under silence command To view all curren...

Страница 12: ...ll be activated instantly bypassing all user programmed delays VIEW ALARMS In alarm state if this key is pressed all current alarms are displayed More details are provided in the next paragraph VIEW F...

Страница 13: ...ecord similar to the figures 2 6 Events menu on the right The figures are samples of an information event and of a fault event The first line indicates GENERAL for information events FAULT for fault e...

Страница 14: ...PLY shows input battery and charging voltage Figure2 9 Panel power supply ALARM COUNTER option displays the total number of alarms recorded in accordance to EN 54 2 Figure2 10 Alarms counter The TESTS...

Страница 15: ...zones that are set in test mode and are also in alarm state This option is meant to be used during maintenance Figure2 15 Alarms in test zones By selecting the POINTS option in the information menu t...

Страница 16: ...CE command is given Please note that RELAY 1 FAULT and RELAY 2 ALARM are not editable by user Only RELAY 3 AUX is editable n terms of functionality mode initial state logic delay and silence Navigate...

Страница 17: ...nel editable via PC software or web interface the network address of the panel and its serial number Figure2 23 Network panels By selecting ETHERNET ADAPTOR option the screen on the right appears When...

Страница 18: ...panel for the CPU and the loop circuits The last line also displays the panel s serial number Note On the screen it is only displayed the firmware for the installed loops e g On the right the screen d...

Страница 19: ...onitor figure 4 1 Figure3 1 Main Menu Then select USER MENU and click Enter A code is required for level 2 access Therefore only authorized users will be able to do any adjustments at this level Figur...

Страница 20: ...agram In this menu the following basic functions can be done RESET the system clears current alarms prealarms and faults SIREN SILENCE in case of an alarm event to mute audible alarm SIREN RESOUND to...

Страница 21: ...zone ALL POINTS all loop devices points except sirens POINTS single loop device point except sirens the panel asks for loop and address of the point ALL SIRENS all conventional and addressable sirens...

Страница 22: ...KING DAYS set the DAY mode days select day with up down keys and enable disable with right key then enter to save setting Monday to Friday by default WORKING HOURS set the working hours from to 06 00...

Страница 23: ...NG will turn off backlight at any state after 1 minute of inactivity The second option BATTERY SAVING will only turn off backlight while on battery power mains interruption after 1 minute of inactivit...

Страница 24: ...p event logs keep a record of current configuration as a backup or to gather and send useful data to manufacturer in terms of troubleshooting When selected a confirmation message as the screen on the...

Страница 25: ...omputer s network settings must be properly adjusted All the settings must be done by the building s network administrator Open a web browser and type the panel s IP address to the URL box e g 10 0 9...

Страница 26: ...nformational options These options are described below 3 7 4 1 Information Panel This option will display the page below with the most significant data of the control panel hardware based 3 7 4 2 Info...

Страница 27: ...hem 3 7 4 5 Information Points This option will open the page below On the input boxes you can enter the point s loop and address By clicking OK the information of the selected point will be displayed...

Страница 28: ...extra relays settings Extra relays belong to peripheral equipment and are not pre installed in the control panel 3 7 4 8 Information Conventional Sirens This page displays all settings for the conven...

Страница 29: ...the high capacity of recorded events 7k the events are divided into pages 3 7 6 User s menu By selecting USER MENU the systems asks for user code access level 2 Enter the user s code and click SEND I...

Страница 30: ...0 60Hz being a Class I product the corresponding terminal contact with the Protective Earth marking inside the device must be connected to the building s ground to ensure proper function and safety Be...

Страница 31: ...a MODBUS adaptor at left side optional There is also a Dip switch selector at the bottom right side of the board which is used to grand access level 4 for specific functions At the bottom left side is...

Страница 32: ...supply lines should cross the wall behind the panel except the panels own power supply The control panel s placement must be to a visible and accessible area to the building attendant and fire safety...

Страница 33: ...Use BATTERY CALCULATOR tool included in BSR 100X software application to calculate the required battery capacity The batteries must be connected in series In the battery area there are two wires one r...

Страница 34: ...hielded cable These connections refer to conventional siren outputs 24VM output 24VP output and loop connection terminals Don t use the same cable for multiple loops or other outputs The connection ca...

Страница 35: ...rt circuit links L to LF and L to LF In order to connect one or more devices to the loop output remove the 2 short circuit links entirely All loop connections are similar A maximum number of 150 devic...

Страница 36: ...Date 22 4 2021 Document number 921100400_09_005 Page 36 of 71 36 71 Figure 4 6 Detector base connections BSR 6155 BSR 6160 and BSR 6157...

Страница 37: ...1 Document number 921100400_09_005 Page 37 of 71 37 71 Figure 4 7 Connecting the manual call point MCP BSR 5136 Figure 4 8 Connecting addressable siren BSR 5132 Figure 4 9 Connection of input output u...

Страница 38: ...sistor must remain on the terminal When sirens are connected to the output the resistor must be removed and placed on the last siren as shown on the figure 4 10 All four circuit connections are identi...

Страница 39: ...tion of a network of panels Figure4 11 Panel network connection Be advised the RS 485 requires 120 resistors on both ends To the panels that are located on the edge of the network a jumper connector m...

Страница 40: ...Date 22 4 2021 Document number 921100400_09_005 Page 40 of 71 40 71 4 6 General connections diagram A theoretical general connections diagram is depicted below Figure4 12 General connections diagram...

Страница 41: ...FAULT Relay Potential free relay contacts that are triggered during a fault event C NC contact circuit active when on fault 30VDC 3A max AUX Relay Potential free relay contacts with a programmable out...

Страница 42: ...ble printer option While the thermal printer is connected and enabled all new events recorded will be printed on paper MODBUS To enable MODBUS communication between the control panel and a Building Mo...

Страница 43: ...which can be granted with hardware access dipswitch selector behind the door To enter Technician menu while on home screen press Enter key once to enter main menu Figure5 1 Main menu Then select TECH...

Страница 44: ...Date 22 4 2021 Document number 921100400_09_005 Page 44 of 71 44 71 Figure5 3 Technician menu diagram In the following sections a detailed description for every available option appears...

Страница 45: ...in test Next the control panel asks for siren mode enabled or disabled By enabling the sirens every time a new alarm event is triggered by any of the connected devices all conventional and addressable...

Страница 46: ...ed of a set of inspection functions used for system inspection after initial installation or troubleshooting 5 2 1 Check points The first option POINTS displays the screen on the right used to check c...

Страница 47: ...ONAL SIRENS option will prompt for selecting a conventional siren output first By clicking Enter key the selected siren output will sound for 6 seconds and then stop in order to confirm functionality...

Страница 48: ...check panel network communication when activated When this option is selected via the Master control panel the top line displays the name MASTER PANEL and the next line indicates the selected subpanel...

Страница 49: ...ctivated during SIREN SILENCE command Some of the options above may not be visible to certain point types Addressable sirens cannot be set to operate in FAULT output mode Figure5 16 Setup points 1 Fig...

Страница 50: ...thin a loop If there is BSR 8120 installed you should temporary disconnect the 24v power to the unit until the autoaddressing procedure is finished When this option is selected the figure 5 19 on the...

Страница 51: ...o not use this function while more than one addressable points are connected to the selected loop 5 3 5 General resound GENERAL RESOUND option will display the screen on the right By selecting YES the...

Страница 52: ...ive negative initial output position Delay switching delay after triggering event Relay silence select if the aux relay output will switch to initial position after SIREN SILENCE command is given Figu...

Страница 53: ...subpanels Figure5 27 Panel address Second option NETWORK SETUP is used to enable or disable panel networking on a control panel When set to enable a master panel enables data transmission via the RS 4...

Страница 54: ...t may detect a fire will send the fire alarm signal to the control panel but will not turn on their red LED indicator By default set to 10 Figure5 31 Max indicators loop 5 3 12 Detectors dependency DE...

Страница 55: ...f a loop or all registered points in the control panel The three available options are the following DELETE SINGLE POINT delete a single point only DELETE LOOP delete all registered points in a loop D...

Страница 56: ...unction EXTERN PCB FUNCTION option is used to select the preferred optional expansion functionality The expansion adaptor may not be pre installed optional therefore in order to operate a mode must be...

Страница 57: ...AN The address is static no DHCP Figure5 44 IP Address Last RESET ETHERNET option re initiates the Ethernet adaptor to fix connection issues or used after IP changing to move to the new IP Figure5 45...

Страница 58: ...event log entries in the control panel This option should be executed after every initial installation so event logs during commissioning are cleared and real time operation events are logged Figure5...

Страница 59: ...iting for a request from the PC During data transmission or reception a relative message TRANSMITTING DATA or RECEIVING DATA will appear on screen Figures5 52 PC Communication 5 8 Technician s Menu on...

Страница 60: ...ions available to configure via web interface that were not present via the keypad 5 8 1 Change information By selecting CHANGE INFORMATION link the page below appears Write down the contractor s cont...

Страница 61: ...tectors should be placed on their detachable base The cable passing across the loop must be in accordance with the initial installation plan otherwise it will be difficult to identify the address of e...

Страница 62: ...addressable devices automatically TECHNICIAN MENU SETUP AUTOADDRESSING ALL LOOPS When the autoaddressing procedure ends if the installation was made according to plan then the control panel will have...

Страница 63: ...ector on the CPU board position Install the BSR 100X software application to a Windows PC connect the control panel to the PC to an available USB port on the PC and launch the application Once you hav...

Страница 64: ...close automatically Now you can proceed with configuring panel parameters Right click on the BSR 100X Panel SN entry on left column and select Edit parameters A window appears with 5 tabs that includ...

Страница 65: ...Edit all other parameters according to the installation needs The last option Connected Device has no effect on the control panel and is only used on the software for loop and battery calculation tool...

Страница 66: ...the same PC COMMUNICATION mode on the control panel the technician is able to receive event log synchronize time with the PC and confirm annual check All these options can be selected in Panel Communi...

Страница 67: ...cture below is appeared It calculates the required battery for the duration of 72 hours of standby and the remaining power for 30 minutes of alarm according to the standards of EN 54 series If we want...

Страница 68: ...ess on each repeater and subpanel should be set and after that address 1 on master panel should be set for network identification 8 5 1 Setup repeater address Repeater address is set from the TECHNICI...

Страница 69: ...circuits 4 x 24VDC 3VDC 300mA max short open circuit monitored 10k termination resistor 24VP Output 24VDC 3VDC permanent output 300mA max short circuit monitored 24VM Output 24VDC 3VDC resettable outp...

Страница 70: ...for operating environment conditions in compliance with 3K5 EN 60721 3 3 1995 9 1 Factory default settings Registered points None Conventional sirens All outputs enabled on general alarm no delay AUX...

Страница 71: ...in the technical leaflet which accompanies each product This warranty ceases to exist if the buyer does not follow the technical instructions included in official documents given by Olympia Electronic...

Отзывы: