13
P/N 30149, Rev. G [12/15/2016]
Check out and adjustments
BML and BMLV furnaces may be used with following oil burners.
Beckett AF, and Riello 40F oil burners are for applications using indoor air for combustion only.
Sidewall venting applications utilizing outdoor air for combustion, use Beckett AFII or Riello 40BF (Balanced Flue) oil burners
only.
Table A-1 Beckett AF Oil Burner Set-Up
Beckett AF Series Oil Burners
(For use with chimney vented units only)
Furnace
Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
Flow Rate
Head
1
Static
Plate
BML-60B2
2
BMLV-60B2²
59,000
AF76BNHS 0.50 / 80°A
100
psig
0.50
usgph
F3
3- ⅜ in.
BML-80B2
BMLV-80B2
76,000
AF76BNHS 0.65 / 80°A
100
psig
0.65
usgph
F3
3- ⅜ in.
BML-90B2
BMLV-90B2
85,000
AF76BNHS 0.75 / 80°A
100
psig
0.75
usgph
F3
3- ⅜ in.
1
Head is shielded by ceramic insulator.
2
Low Firing Rate Baffle required when using 0.50-gallon nozzle.
Table A-2 Beckett AFII Oil Burner Set-Up
Beckett AFII Series Oil Burners
(For use with sidewall vented units with outdoor combustion air,
or chimney vented units with indoor air for combustion)
Furnace Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
Flow Rate
Head
BML-60BB2U2
BMLV-60BB2U2
59,000
AFII-85
0.50 / 60°A
115
psig
0.50
usgph
FB0
BML-80BB2U2
BMLV-80BB2U2
76,000
AFII-85
0.60 / 60°A
145
psig
0.65
usgph
FB3
BML-90BB2U2
BMLV-90BB2U2
88,000
AFII-85
0.70 / 60°A
145
psig
0.75
usgph
FB3
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Содержание BML-60B22
Страница 20: ...20 P N 30149 Rev G 12 15 2016 APPENDIX B WIRING DIAGRAMS Chimney Vent Furnace Wiring Diagram BML BMLV...
Страница 21: ...21 P N 30149 Rev G 12 15 2016 APPENDIX B WIRING DIAGRAMS Direct Vent Furnace Wiring Diagram BML BMLV...
Страница 31: ...31 P N 30149 Rev G 12 15 2016 Model BML and BMLV Diagram Direct Drive Model Shown 37...
Страница 32: ...P N 30149 Rev G 12 15 2016 ECR International 2210 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...