Table A-3 Riello 40F Series Oil Burner Set-Up
Riello 40F Series Oil Burners
(For use with chimney vented units)
Furnace Model Output
BTU/Hr
Burner
Model
Delavan Nozzle
Pump
Pressure
Flow Rate
Air Gate
Turbulator
Setting
BML-60BRF2
BMLV-60BRF2
60,000
40F3
0.50 / 60°W
105
psig
0.50
usgph
2.6
1.0
BML-80BRF2
BMLV-80BRF2
77,000
40F3
0.60 / 60°W
120
psig
0.65
usgph
2.6
1.5
BML-90BRF2
BMLV-90BRF2
88,000
40F3
0.65 / 60°W
135
psig
0.75
usgph
3.6
2.0
Table A-4 Riello Balanced Flue (40BF) Burner Set-Up
Riello 40BF Balanced Flue Series Oil Burners
(For use with sidewall vented units using outdoor combustion air)
Furnace Model
Output
BTU/Hr
Burner
Model
Delavan
Nozzle
Pump
Pressure
Flow Rate
Turbulator
Setting
BML-60BRBU2
BMLV-60BRBU2
61,000
40BF3
0.50 / 60°W
105
psig
0.50
usgph
1.0
BML-80BRBU2
BMLV-80BRBU2
78,000
40BF3
0.60 / 60°W
120
psig
0.65
usgph
1.5
BML-90BRBU2
BMLV-90BRBU2
89,000
40BF3
0.65 / 60°W
135
psig
0.75
usgph
2.0
NOTE
: Air gate setting may vary for sidewall vented units where air gate must be adjusted to achieve zero smoke.
A.1 OIL BURNER AIR ADJUSTMENT
Consult oil burner instructions provided in furnace
documents envelope for specific information concerning
burner adjustments, operation and troubleshooting.
Beckett AF Burner (Chimney Vent)
Adjust air shutter by loosening locking screws. Moving air
shutter, and if necessary, bulk air band.
Beckett AFII Burner (Direct Vent)
Adjust burner air supply. Loosen locking screw located on
black dial to right of burner. Turn black dial clockwise to
increase combustion air and counter-clockwise to decrease
combustion air. Re-tighten locking screw after obtaining
proper setting.
Riello 40F3 Burner (Chimney Vent)
Combustion air is adjusted by removing burner cover.
Loosen screws that secure air adjustment plate. Move
adjusting plate to either increase or decrease combustion
air. When proper air setting is achieved, retighten fixing
screws.
Riello 40BF3 Burner (Direct Vent)
Combustion air can be adjusted with burner cover on.
Remove plastic cover on top right hand side of burner
cover. With phillips head screw driver, turn adjustment
screw clockwise to increase combustion air or counter-
clockwise to decrease combustion air. When combustion air
is set, re-insert plastic cover.
APPENDIX A - CHECK OUT AND ADJUSTMENTS
Содержание BML-60B22
Страница 20: ...20 P N 30149 Rev G 12 15 2016 APPENDIX B WIRING DIAGRAMS Chimney Vent Furnace Wiring Diagram BML BMLV...
Страница 21: ...21 P N 30149 Rev G 12 15 2016 APPENDIX B WIRING DIAGRAMS Direct Vent Furnace Wiring Diagram BML BMLV...
Страница 31: ...31 P N 30149 Rev G 12 15 2016 Model BML and BMLV Diagram Direct Drive Model Shown 37...
Страница 32: ...P N 30149 Rev G 12 15 2016 ECR International 2210 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...