LB51100 Installation and User Manual
7
Shenzhen Olipower Energy & Automation Technology., Ltd
High voltage may cause an electric shock, which results in serious injury,
death, or serious property damage from the LB51100 in operation. Prior to maintenance, power off
the LB51100 and strictly comply with the safety precautions in this document and associated
documents to operate the
LB51100
.
Maintain the LB51100 with sufficient knowledge of this document, proper
tools, and testing equipment.
Before performing maintenance tasks, power off the LB51100 and wait at least
5 minutes.
Temporary warning signs or fences must be placed to prevent unauthorized
people from entering the site.
If the LB51100 is faulty, contact your supplier.
The LB51100 can be powered on only after all faults are rectified. Failing to do so
may escalate faults or damage the device.
Observe ESD precautions and wear ESD gloves during maintenance.
Regular Maintenance
Items
Time
Cleaning case using soft cloth
Once 6 months
Cleaning ventilation hole using soft brush
Once a year
Discharge to SOH 50% when not to use in 3month
On demand
Fully charge discharge to SOH 25%
Once a year
Disposal
The battery energy storage system must not be disposed of with domestic waste to
fulfill the regulations and legal enquiry. The user has the responsibility and
obligation to send it to the designated organization for recycling and disposal.
5
System Installation
5.1
Installation notice
a)
Before installation, check the battery open circuit voltage.
b)
Battery installation location should be away from heat and avoid produce spark. The safety distance should be
above than 0.5m.
c)
Battery installing connecting cables should be as short as possible, to prevent excessive line pressure drop.
d)
Batteries with different capacity, different P/N or different manufactures are not allowed for connection.
e)
Before conducting the battery, the battery positive and negative poles need to be carefully checked as well to
ensure correct installation.
f)
The mounting floor should be horizontal.
g)
The battery IP Rating is IP20 and is for indoor installations only.
h)
For Australian market, the battery energy storage system can only be mounted into battery cabinet or rack using screw firmed
tightly and racks can be stand together without space. And distance between batteries is 5mm as least. Battery cabinets/racks
are not provided with battery and are outside the scope of product certification.
i)
Distances of any standoff from a wall, floor, ceiling/roof is 0.5m at least; Distance from any heat source (e.g. hot water
systems, gas heaters or the like) is 0.5m at least; Distance/clearances from any equipment/wall/structure to the sides, bottom,