MAESTRO SMART

US-ENG- 7

US-ENGLISH

2.3 -  CHOOSING THE POSITION OF THE UNIT

 (fig.2-3)

the unit must be installed on a wall that directly communicates with the outside. the position for installing 
the unit must have the following prerequisites:

•  The height of the unit’s lower edge from the floor should be at least 4”(100 mm) if installed on the wall 

in the lowest position.

•   If installed on the wall in the highest position, it should be at least 3.5”(90 mm) from the ceiling.

•   The wall on which the inside unit is installed must be of sufficient strength to withstand its weight.

•   There must be adequate space around the unit for any maintenance or service that may be necessary.

•   There should be nothing in the way of the air that needs to circulate both on the top return air (curtains, 

plants, furniture) or at the front where the air exits (supply air). this could cause air swirls that could effect 

the unit performance and efficiency.

•  It must be possible to leave room around the unit for any maintenance operations that may be necessary.

 

When selecting the unit’s location as described above the installer must insure there are no 
structures or systems (beams, piers, pipes, wires, etc.) at the points where the holes are to be 

drilled. Interference from any item would prevent drilling the holes required to install the unit.

•  The unit should not be placed under curtains that may block free movement of the air.

•  Do not spray water or other liquids of any kind directly on the unit.

•   The unit should not be installed in a position where the airflow is directed towards occupants in the 

conditioned space.

•   Never force open the supply air flap.

•   Do not place any other object on the air grille that may even partially obstruct the grille itself.

•  The unit should not be installed directly over another appliance, such as a television set, radio, refriger

-

ator, etc., or over any other source of heat.

•  Do not store anything on the unit as it will limit airflow, reduce capacity and increase energy costs.

•  Do not attempt to manually open or close the modulating damper or spray corrosive cleaning agents 

into the unit.

•  Do not allow curtains or other hanging materials to block the flow of air entering or exiting the unit.

•  Do not allow airflow to be directed towards occupants as their comfort will be negatively impacted. Also, 

do not install the unit in close proximity to heat producing appliances or devices.

2.4 -  UNIT ASSEMBLY

the maximum length allowed for the wall sleeves is 39” (990 mm). the wall sleeves must be smooth on the
inside with a diameter of 8” (200 mm). Wall sleeves cannot be curved or bent. it is strongly recommended
to use the louvred grilles provided, or if other grilles are to be used, they must be factory approved to

avoid capacity or efficiency issues due insufficient air flow.

2.4.1 - 

DRILLING THE WALL (

fig

.4-5-6)

install the unit by drilling two holes (diameter of both pipes must be either 8”(200 mm) or 6.4”(160 mm) 
through the wall as indicated on the drilling installation template. the 8”(200 mm) holes will ensure the best 
performance and lowest air noise level. Drill the wall using the proper tools, taking care to prevent excess 
damage to the wall or surrounding areas. 

Содержание Maestro Smart

Страница 1: ...SMART ENG INSTRUCTIONS FOR INSTALLATION USE AND MAINTENANCE...

Страница 2: ......

Страница 3: ...nit peut tre utilis e par des enfants d au moins 8 ans et par des personnes ayantdescapacit sphysiques sensoriellesoumentalesr duites oud pourvues de l exp rience ou des connaissances n cessaires cond...

Страница 4: ...orelfabricante por su servicio de asistencia t cnica o por personal con cualificaci n similar con el fin de prevenir cualquier riesgo para el usuario final 5 La instalaci n la primera puesta en marcha...

Страница 5: ...RT FRA ENG DIRECTIVES D INSTALLATION D UTILISATION ET D ENTRETIEN INSTRUCTIONS FOR INSTALLATION USE AND MAINTENANCE ESP INSTRUCCIONES DE INSTALACI N USO Y MANTENIMIENTO FRA ESP ENG 1 2 H C L A D G E B...

Страница 6: ...3 A 4 5...

Страница 7: ...min 300mm min 12 8mm 8 6 7 9 H G G min 200mm min 8 10 11 G 6a...

Страница 8: ...12 F D F G 13 14 6mm 15 16 F...

Страница 9: ...19 17 20 18 E E E 21...

Страница 10: ...H L A L 24 22 23 25 26 27...

Страница 11: ...32 30 31 J1 P1 P1 P2 28 29 33 9...

Страница 12: ...34 10 9 35 3 F 36 37 F1 F2 F1 F2...

Страница 13: ...sate water during an emergency 13 2 6 roUtine maintenanCe 13 2 6 1 Cleaning the air filter 13 3 USE AND MAINTENANCE 14 3 1 WarninGS aBoUt eQUiPment USe 14 3 2 DeSCriPtion of tHe WarninG Panel 14 3 3 U...

Страница 14: ...rstosituationsinwhichyoushouldinformtheServiCedepartmentinthecompany CUSTOMER TECHNICAL SERVICE 1 800 408 5196 techsupport olimpiasplendidusa com Index Paragraphs marked with this symbol contain very...

Страница 15: ...user this section contains useful information for understanding the use and programming of the unit and the most common maintenance recommendations 2 This document contains proprietary information pro...

Страница 16: ...on the labels affixed inside the unit and use common sense and follow the safety regulation enforced in the place of installation 10 Always wear personal protection devices when servicing the unit The...

Страница 17: ...rial The units are shipped complete and in perfect condition when leaving the manufacturing plant However we suggest that you perform the following checks a Upon receipt check if the package is damage...

Страница 18: ...WILL BE INSTALLED Before selecting an air conditioner or heat pump it is essential to make an accurate calculation of the heat load including sensible and latent gains for cooling mode and for heat pu...

Страница 19: ...d not be installed in a position where the airflow is directed towards occupants in the conditioned space Never force open the supply air flap Do not place any other object on the air grille that may...

Страница 20: ...ied out incorrectly When installing heat pump models if no condensate line are built into the wall it will be necessary to drill a hole through the wall as shown on the installation template 2 4 2 PRE...

Страница 21: ...ompletely outwards reopen the grille being careful to keep your fingers inside the louvres h turn the grille until the louvres are fully horizontal and tilted downwards i Pull the chain tensioning the...

Страница 22: ...trical power supply is equipped with efficient grounding and with adequate protections against overloading and or short circuits a type 15 AT delayed fuse or other devices with equivalent functions ar...

Страница 23: ...he pin P1 on the right hand side of the fap e insert the fap into the unit by inserting the pin into the top hole on the right hand side in the opening P2 and the flap s left hand hole on the upper pi...

Страница 24: ...below to determine the cause DESCRIPTION LED D GREEN LED C YELLOW LED B GREEN LED A RED overtemperature of internal heat exchanger Hti off off on off overtemperature of external heat exchanger Hte of...

Страница 25: ...more thorough cleaning can be performed using non acidic environmentally friendly detergents and use a damp cloth to gently clean the surface of the unit To prevent unnecessary service calls from the...

Страница 26: ...unit is in heating mode it may go into defrost mode to melt any ice that could have formed on the condenser coil While it is doing this the machine keeps running but does not heat the space The defro...

Страница 27: ...the unit there may be interference Electronic and fluorescent lighting may interfere with communications between the remote control and the unit If not being used for an extended period of time remov...

Страница 28: ...programs T7 Button for increasing or decreasing the temperature time settings T8 Button for activating the free CoolinG air change system not available in this model T9 ON OFF button for oscillating f...

Страница 29: ...Clock program setting D16 Program switching on time setting D17 Low battery notification D18 minutes timer 3 3 3 UNIT START UP fig 34 to operate the unit using the remote control it will be necessary...

Страница 30: ...B being illuminated green 3 4 4 DEHUMIDIFICATION MODE in this mode the unit lowers the humidity level in the space This function is very useful during the shoulder months between cooling and heating...

Страница 31: ...evel By selecting automatic mode the microprocessor adjusts the fan speed as required using the following logic As the difference between the actual room temperature and the end user setpoint increase...

Страница 32: ...h the timer programming 3 5 3 TIMER SETTING PROGR 1 AND PROGR 2 fig E1 it is possible to set one or both the timer programs to set the times for starting and stopping the unit proceed as follows a Pre...

Страница 33: ...ng the shades Do not obstruct the air flow from either the inlet or outlet of the unit Obstructing airflow results in reduced performance and will eventually damage the unit 3 7 Diagnostic Recommendat...

Страница 34: ...mote control and the unit s reception confirmation sound will not work when you attempt to issue a command if this is the case replace the batteries The unit does not cool or heat adequately the tempe...

Страница 35: ...Starting the unit verify Supply voltage to the unit _______ install batteries in remote Control Start Unit to verify operation and record requested values below the following values are to be recorde...

Страница 36: ...Changes in the appearance of the product that do not affect product performance 14 increases in utility costs and additional utility expenses 15 a completed data sheet available on www olimpiasplendi...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...262089C 2 Contact Information olimpia Splendid USa 66 White Street floor 501 new York nY 10013 USa Phone fax 800 408 5196 email customerservice olimpiasplendidusa com...

Отзывы: