8
FUNCTIONALITY
DESCRIPTION
CONTROLLER
BUTTON
ICON
LED
ACOUSTIC
SIGNAL
Airflow direction
Alternate
The unit runs in extract/intake at the selected speed: the inversion
time is automatically defined thanks to the integrel temperature sensor
(comfort mode).
green
short
Extract
The unit runs in extract only at the selected speed.
green
short
Intake
The unit runs in intake only at the selected speed.
green
short
Mode (active only if the airflow direction is set on alternate)
Comfort
Optimisation of the acoustic and thermal comfort. The inversion time
varies automatically from 40÷120 seconds, thanks to the integrel
temperature sensor. The first time cycle is of 70 seconds, then it varies
automatically according to the detected temperature conditions.
green
short
Efficiency
Optimisation of the thermal efficiency. The inversion time is fixed at
about 70 seconds.
green
short
Continuous running speed
Speed 1: 20m
3
/h
green
short
Speed 2: 30m
3
/h
green
short
Speed 3: 40m
3
/h
green
short
Speed 4: 50m
3
/h
green
short
Speed 5: 60m
3
/h
green
short
Off position
Pressing the button for 3 seconds, the units switches off, emitting a
long acoustic signal. To re-activate the unit, press or .
red
long
BOOST speed
The unit runs at speed 5 (maximum) for 15 minutes, in extract only;
then it returns to the previously selected mode/speed. The BOOST
speed cannot be activated if the controller is OFF.
fixed blue
short
Free cooling
The unit runs in “extract only” or “intake only” to avoid heat recovery
when not needed.
green
short
COMFORT
EFFICIENCY
OFF
or
―
+
―
+
―
+
―
+
―
+
―
―
Filter reset
Every 3 months a yellow warning led switches on (fixed light) to indicate
that the filters have to be maintained. Press the dedicated button for 5
seconds to reset the timing.
green
short
Smart humidity control
When the humidity sensor detects a quick variation of the Relative
Humidity level, the running speed automatically increases to the next
higher speed. After 10 minutes from the last quick RH variation, the
unit returns running at the selected speed. The smart humidity control
is active if the airflow direction is set on alternate or extract only: if
speed 5 has been selected, no speed increase happens. To disable this
functionality, press the button for 5 seconds: on the top side of the
LCD display the symbol is shown.
flashing
blue
Antifrost
This functionality prevents frost building up on the heat exchanger due
to extremely cold air. When it is activated, the unit runs in extract only
at speed 1, for 30 minutes.
fixed red
Acoustic signal
Any time a setting is transferred from the controller to the unit, a short
acoustic signal is emitted. This can be deactivated by pressing the
cgfgf
button for 7 seconds, after when a green led flashes to indicate that the
acoustic signal is off. To reactivate the acoustic signal repeat the same
operation for 7 seconds until the led becomes green and an acoustic
signal is emitted.
green
short
FILTER
RESET
+