4
– Installation
54
Equipment required
■
Complete detector.
■
Connection cable.
■
Tools for mounting the device.
■
Mounting materials.
Positioning the detector
The detector should be positioned at ground level, on the ceiling, at the height
of the respiratory tract or near air extraction ducts, depending on the application
or the density of the gas to be detected. Heavy gases should be detected at
ground level, while light gases should be detected at ceiling height.
Mounting the detector
All versions with local sensor
The detector must be installed with the detection sensor pointing downwards.
For combustible gas detectors, tilting the device more than 45° past vertical can
lead to imprecise readings.
The housing should be mounted using 4 M6 screws and appropriate anchors
for the mounting surface.
Figure 37: sensor pointing downward (left); maximum angle for an combustible
gas detector (right).
All versions with remote sensor
For combustible gas detectors, tilting the sensor more than 45° past vertical can
lead to imprecise readings.
The housing should be mounted using 4 M6 screws and appropriate anchors
for the mounting surface. The sensor pack should be mounted using 2 M4
screws and appropriate anchors for the mounting surface.
Содержание olct 80
Страница 1: ...1 User manual OLCT 80 Part Number NPO80GB Revision E 1 The Fixed Gas Detection Experts...
Страница 6: ...Table of Contents vi...
Страница 10: ...1 Overwiew 4...
Страница 18: ...2 Transmitter Overview 12...
Страница 22: ...3 Menus 16 Figure 15 the OLCT 80 s sub menus under AFF MES DATE TIME and PROG...
Страница 23: ...3 Menus 17 Figure 16 the OLCT 80 s sub menus under MAINT CALIBRA 4 20mA INFOS and TEST...
Страница 35: ...3 Menus 29 Figure 23 the ANA1 Configuration menu Press ESC repeatedly to return to the reading display...
Страница 39: ...3 Menus 33 Figure 25 the Alarm Relay Configuration menu Press ESC repeatedly to return to the reading display...
Страница 42: ...3 Menus 36 Figure 26 RELAY 1 menu Press ESC repeatedly to return to the reading display...
Страница 46: ...3 Menus 40 Figure 28 the Alarm Relay Configuration menu Press ESC repeatedly to return to the reading display...
Страница 58: ...3 Menus 52...
Страница 74: ...5 Wireless Version 68...
Страница 82: ...7 Pre installation Hardware Configuration 76...
Страница 84: ...8 Preventative Maintenance 78...
Страница 90: ...10 Accessories 84...
Страница 96: ...12 EU Declarations of Conformity 90 OLCT 80 without antenna...
Страница 97: ...12 EU Declarations of Conformity 91...
Страница 98: ...12 EU Declarations of Conformity 92 OLCT 80 with antenna...
Страница 99: ...12 EU Declarations of Conformity 93...
Страница 100: ...12 EU Declarations of Conformity 94 IR20 remote control of the OLCT 80...
Страница 108: ...13 Technical Specifications 102...
Страница 116: ...14 Special instructions for use in explosive environments and fonctional safety 110...
Страница 119: ...113...