3
– Menus
28
PG CH1
Purpose
Configure the
ANA1
sensor.
How to access
See Figure 21.
Tree structure
See Figure 23.
Menu
Description
ON
Turn the
ANA1
sensor on or off.
PRINCIPAL
■
Display
: display the reading from the
ANA1
sensor.
■
Primary
: display the reading from the
ANA1
sensor and go to the
4-20 mA menu (see step below).
■
Secondary
: the reading is not displayed.
Note: if multiple sensors (main sensor, ANA1 sensor or ANA2
sensor) are configured as the
Primary
, the -4-20 mA output will use
the current corresponding to the
Main sensor
.
4-20 mA
Define the output current type (see the
Note on the 4-20 mA current
type
on page 27).
■
Normal
: standard 4-20 mA signal.
■
Combined
: signal uses predefined values representing the alarm
statuses of the 3 sensors. This option is automatically selected if
the
Secondary
option was defined in the previous step.
■
CAPEX
: all-or-nothing signal indicating normal operation or a fault
condition.
Measure
■
Reading
: the channel will be used to input an analog reading (4-
20 mA current only).
■
Acknowledge
: the channel will be assigned to a dry contact for
remote acknowledgment (function used only in the absence of the
IR20 remote control). The contact will be wired between the
S
and
E
terminals of the 4-20 mA input, labeled
IN1.
See Figure 5, 2 .
% LEL
Defines the unit of measure displayed on the LCD (%LEL, %O2, %,
ppm H2S, ppm NH3, ppm HCL, ppm CO2, ppm NO, ppm ETO, ppm
H2, ppm HCN, ppm HF, ppm O3, ppm CLO2, ppm, ppb, °C, V, hPa,
[blank]).
Display
Define the position of the decimal point, e.g., 22.22.
Gamme
Define the reading range on the LCD (001-100 in increments of one,
100-1000 in increments of ten or 1000-9900 in increments of one
hundred).
Zero in V
Define the bottom of the range in volts.
0.48 V corresponds to 4 mA through a 120 ohm resistor.
Scale in V
Define the top of the range in volts.
2.40 V corresponds to 20 mA through a 120 ohm resistor.
Coef
Defines the reading integration time (none, 5 seconds, 30 seconds,
1 minute, 2, 5, 10 or 15 minutes). The reading will be averaged over
the given period.
Содержание olct 80
Страница 1: ...1 User manual OLCT 80 Part Number NPO80GB Revision E 1 The Fixed Gas Detection Experts...
Страница 6: ...Table of Contents vi...
Страница 10: ...1 Overwiew 4...
Страница 18: ...2 Transmitter Overview 12...
Страница 22: ...3 Menus 16 Figure 15 the OLCT 80 s sub menus under AFF MES DATE TIME and PROG...
Страница 23: ...3 Menus 17 Figure 16 the OLCT 80 s sub menus under MAINT CALIBRA 4 20mA INFOS and TEST...
Страница 35: ...3 Menus 29 Figure 23 the ANA1 Configuration menu Press ESC repeatedly to return to the reading display...
Страница 39: ...3 Menus 33 Figure 25 the Alarm Relay Configuration menu Press ESC repeatedly to return to the reading display...
Страница 42: ...3 Menus 36 Figure 26 RELAY 1 menu Press ESC repeatedly to return to the reading display...
Страница 46: ...3 Menus 40 Figure 28 the Alarm Relay Configuration menu Press ESC repeatedly to return to the reading display...
Страница 58: ...3 Menus 52...
Страница 74: ...5 Wireless Version 68...
Страница 82: ...7 Pre installation Hardware Configuration 76...
Страница 84: ...8 Preventative Maintenance 78...
Страница 90: ...10 Accessories 84...
Страница 96: ...12 EU Declarations of Conformity 90 OLCT 80 without antenna...
Страница 97: ...12 EU Declarations of Conformity 91...
Страница 98: ...12 EU Declarations of Conformity 92 OLCT 80 with antenna...
Страница 99: ...12 EU Declarations of Conformity 93...
Страница 100: ...12 EU Declarations of Conformity 94 IR20 remote control of the OLCT 80...
Страница 108: ...13 Technical Specifications 102...
Страница 116: ...14 Special instructions for use in explosive environments and fonctional safety 110...
Страница 119: ...113...