58
OLC(T)100
Technical manual
The detector may be opened in a gaseous explosive zone (dusty non-explosive)
only to change the sensor block or for maintenance or to connect a compatible
intrinsically safe voltmeter with the following characteristics:
•
Certified for use in explosive atmospheres (Group IIc), no generator of
current or voltage
•
Ui max <= 28V; Ii max <= 93.3 mA
•
Li
≤
3.5 mH
•
Ci
≤
44 nF under 28V ; Ci
≤
20 nF under 10.5 V ; Ci
≤
0.88 µF under
8.6V