Measures against Faults
Display:
Possible Cause:
Measures against Faults:
LED for ‘fault’
Line disconnection
Insulation defect
Defective transducer
Wrongly connected line
A transducer has exceeded
24.5mA.
(Attention! Danger!)
Measure signal current
Check connection
Check gas concentration sepa-
rately
Exchange transducer
Part of the LEDs for
‘fault’ is on and another
part is off;
no LED for system in-
formation is on.
An analog input module is de-
fective or not connected.
Several transducers have, for
example, been contaminated.
Check connection between ana-
log input module and controller
module
Check 24V supply
Check address of analog input
module
Replace analog input module
Check configuration with PC
software ConfigPro
All LEDs for excess of
measuring range and in-
sufficient signal are
blink- ing; the remaining
LEDs for channel and
system information are
off
Communication error between
controller module and display
(In this case, safety functions
are fully maintained via the
relays.)
Evaluate fault indication on the
controller module
Check connection between con-
troller module and display
LED for ‘single mode’ is
blinking
Malfunction of controller B
Evaluate fault indication on the
controller module
LED for ‘single mode’
and all LEDs for ‘fault’
are blinking
Malfunction of controller A
Evaluate fault indication on the
controller module
LED for ‘system failure’
is blinking
Both controllers of the con-
troller module are defective.
Interruption of connection to
all analog input modules
Interruption of connection to
at least one relay module
Evaluate fault indication on the
controller module
Check connection between ana-
log input module and controller
module
Check connection between re-
lay module and controller
module
LED for ‘battery’ is
blink-ing
Emergency power supply
Check mains supply
All LEDs for ‘fault’ and
‘operation’ are blinking
Power failure logic in opera-
tion – no malfunction!
After the time preset for power
failure logic, the system auto-
matically turns to normal op-
eration.
Содержание MX62
Страница 54: ...55...
Страница 57: ...58 Permits to choose the language which will be used into the software...
Страница 58: ...59 The screen displays the different possibilities of the COM62 software...
Страница 59: ...60 Examples of programmed possibilities...
Страница 64: ...65 Configuration up to the inputs measurement channel type...
Страница 66: ...67 configuration of detector s caracteristics...
Страница 67: ...68 Test calibrating up to a detector...
Страница 68: ...69 Permits to analyse for a defined detector the zero and sensitivity derives...
Страница 75: ...76 Putting into memory of some used parameters type connection of 4 20mA in accordance with values...
Страница 77: ...78 Allows to choose a type of pre programmed detector...
Страница 78: ...79 Allows to define a detection profile...
Страница 79: ...80 Profile continuation type of alarm...
Страница 80: ...81 Type of alarm continuation...
Страница 81: ...82 Type of alarm continuation...
Страница 82: ...83 D DA AT TA AL LO OG GG GE ER R A AN ND D L LI IN NE EP PR RI IN NT T E ER R S SE ET TT T I IN NG GS S...
Страница 84: ...85...