9
– Special Instructions
71
Chapter 9
| Special Instructions for
use in explosive
atmospheres or
hazardous locations
Information in following paragraphs must be taken into account and followed by the
person responsible for the equipment installation site. Refer to the provisions of
European ATEX Directive 1999/92/EC or to the applicable local legislation, relevant to
improving safety protection and health of workers exposed to the risks of explosive
atmospheres.
The installation and maintenance of the gas monitor should be performed according to
standards EN/IEC 60079-14 and EN/IEC 60079-17.
For intrinsically safe installations and especially for connections to the gas monitor, the
person responsible for the intrinsic safety installation, called the
System designer
, must
establish a system document demonstrating that the entire gas monitor system - Cable -
Body is Intrinsically Safe (see standard IEC 60079-25 for the preparation of this
document).
The BM 25/25W complies with the following standards:
ATEX
IECEx
EN 60079-0:2012
IEC 60079-0 (ed. 6), 2011
EN 60079-1:2007
IEC 60079-1 (ed. 6), 2007
EN 60079-11:2012 IEC 60079-11 (ed. 6), 2011
EN 60079-26:2007 IEC 60079-26 (ed. 2), 2007
EN 50303:2000
Содержание BM25
Страница 1: ...BM 25 25W Area Gas Monitor Part Number NPB25EN Version L 2 User Manual ...
Страница 8: ...8 BM 25 25W Instruction Manual ...
Страница 10: ...10 BM 25 25W Instruction Manual Product Overview Figure 2 Product Overview ...
Страница 18: ...18 BM 25 25W Instruction Manual ...
Страница 34: ...34 BM 25 25W Instruction Manual ...
Страница 70: ...70 BM 25 25W Instruction Manual ...
Страница 76: ...76 BM 25 25W Instruction Manual ...
Страница 78: ...78 BM 25 25W Instruction Manual ...
Страница 79: ...10 Declaration of EC Conformity 79 ...