14
BM 25/25W
Instruction Manual
Relay Outputs (black ring)
■
Pins 1-6: alarm relay (NO) output
■
Pins 3-4: fault relay (NC) output
Unused connectors must be equipped
with their protective cap.
See details on pages 21 and 57.
Figure 6: relay outputs
Dry logic inputs (yellow ring)
■
Pin 2: logic input for alarm transfer
■
Pin 5: logic input for alarm acknowledgement
■
Pin 7: common ground
Unused connectors must be equipped
with their protective cap.
See details on pages 22 and 57.
Intrinsic safety parameters
■
Alarm relay output: dry relay contact,
Ui = 30 V, Ii = 150 mA, no L or C
condition
■
Power supply for trickle charging: Ui = 30 V,
Ii = 160 mA, no L or C condition
■
Dry logic input: Uo = 5 V, Io = 50 mA, Lo = 8
mH, Co = 7 µF
Figure 7: dry logic inputs
The person responsible for the gas monitor must create a Descriptive
System Document (for intrinsically safe circuits).
Содержание BM25
Страница 1: ...BM 25 25W Area Gas Monitor Part Number NPB25EN Version L 2 User Manual ...
Страница 8: ...8 BM 25 25W Instruction Manual ...
Страница 10: ...10 BM 25 25W Instruction Manual Product Overview Figure 2 Product Overview ...
Страница 18: ...18 BM 25 25W Instruction Manual ...
Страница 34: ...34 BM 25 25W Instruction Manual ...
Страница 70: ...70 BM 25 25W Instruction Manual ...
Страница 76: ...76 BM 25 25W Instruction Manual ...
Страница 78: ...78 BM 25 25W Instruction Manual ...
Страница 79: ...10 Declaration of EC Conformity 79 ...