OLCT 700/710 TP
Page 30 of 45
Rev. C.1
OLCT 700/710 TP Instruction Manual
a) Remove power to OLCT 700/710 TP detector by lifting the + 24VDC wire in J-Box.
NOTE
: It is necessary to remove power while changing the plug-in H
2
S sensor in order to
maintain area classification.
b) Use a M1.5 Allen wrench to release the locking setscrew that locks the ITM and bottom housing
together (One turn will suffice - Do not remove setscrew completely).
c) Remove splashguard. Unthread and remove the Bottom Housing from the ITM.
d) Gently pull the plug-in H
2
S sensor cell out of the ITM. Orient the new plug in sensor so that it matches
with the female connector pins. It may be necessary to look from below to assure alignment is correct.
When properly aligned, press the sensor in firmly to make the proper connection.
e) Thread the Bottom Housing onto the ITM to a snug fit and tighten the locking setscrew using the 1/16”
Allen wrench. Reinstall the splashguard.
f) Perform “Set Heater Power (Section 3.5.6 to match the new sensor with the ITM. Perform a successful
AutoSpan to match the new sensor with the ITM (Section 3.4).
Содержание 700 TP Series
Страница 6: ...OLCT 700 710 TP vi OLCT 700 710 TP This page has been left blank intentionally...
Страница 20: ...OLCT 700 710 TP Page 14 of 45 Rev C 1 OLCT 700 710 TP Instruction Manual...
Страница 44: ...OLCT 700 710 TP Page 38 of 45 Rev C 1 OLCT 700 710 TP Instruction Manual 7 3 OLCT 700710 TP Drawings...
Страница 46: ...OLCT 700 710 TP Page 40 of 45 Rev C 1 OLCT 700 710 TP Instruction Manual...
Страница 47: ...OLCT 700 710 TP OLCT 700 710 TP Instruction Manual Rev C 1 Page 41 of 45 8 EU Declaration of conformity...
Страница 48: ...OLCT 700 710 TP Page 42 of 45 Rev C 1 OLCT 700 710 TP Instruction Manual...