OLCT 700/710 TP
Page 8 of 45
Rev. C.1
OLCT 700/710 TP Instruction Manual
2.5
Mounting Installation
▪
The installation should meet all the regulations currently in force for installations in explosive
atmospheres, in particular the standards IEC/EN 60079-14 and IEC/EN 60079-17 (whichever editions
are in force) or in accordance with other national standards.
▪
The equipment is allowed in ATEX zones 1 and 2 for ambient temperatures ranging from -40 °C to +
75 °C. Understand that operating temperature range may be different (see technical specifications).
▪
The sensor shall always be in contact with ambient air. Therefore,
- do not cover the detector
- do not paint detector assemblies
- avoid dust accumulation
The OLCT 700/710 TP should be vertically oriented so that the detector points straight downward (see
Figure below). Installation of the enclosure shall be secured with 4 x M6 screws and the appropriate plugs
for the supporting material. There is an adaptor plate for ceiling installation (PN 6322420).
Figure 6:
Outline and Mounting Dimensions
When mounting on a pole, secure the Junction Box to a suitable mounting plate and attach the mounting
plate to the pole using U-Bolts (Pole-Mounting brackets for Oldham J-box accessories are available
separately).
Ground
Ground
Содержание 700 TP Series
Страница 6: ...OLCT 700 710 TP vi OLCT 700 710 TP This page has been left blank intentionally...
Страница 20: ...OLCT 700 710 TP Page 14 of 45 Rev C 1 OLCT 700 710 TP Instruction Manual...
Страница 44: ...OLCT 700 710 TP Page 38 of 45 Rev C 1 OLCT 700 710 TP Instruction Manual 7 3 OLCT 700710 TP Drawings...
Страница 46: ...OLCT 700 710 TP Page 40 of 45 Rev C 1 OLCT 700 710 TP Instruction Manual...
Страница 47: ...OLCT 700 710 TP OLCT 700 710 TP Instruction Manual Rev C 1 Page 41 of 45 8 EU Declaration of conformity...
Страница 48: ...OLCT 700 710 TP Page 42 of 45 Rev C 1 OLCT 700 710 TP Instruction Manual...