5.4.8 External alarm
This view is used to configure the settings for an external alarm signal that can be
connected to the heat pump.
External alarm ver. 1
The
Level
setting determines how the heat pump will respond to an external alarm
signal.
● If set to
Info
, an alarm will be generated and displayed in the user interface.
● If set to
Fatal
, the heat pump's compressors will not start.
You can connect the external signal to either input 17 or 18.
5.4.9 Soft starter alarms
This view allows you to enable and disable alarms for the soft starter. The available
options are
Soft starter
and
Phase guard
.
5.4.10 Super heat circuit control: desuperheater control options
This view allows you to change the desuperheater pump’s settings.
Super heat circuit control ver. 1
The
Rinse interval
option determines the number of days after which the pump
completes a rinse cycle. The heat pump is rinsed during the first operating cycle of the
day.
The
Manual control
option allows you to specify a speed setting for the pump.
52 (70)
M8011 2204EN