Heat value for light fuel oil approx. 11,86 kWh/kg and for heavy fuel oil approx. 11,22
kWh/kg. Check exact values from supplier.
Turn OFF preheater when using light fuel oil
The shape of the boiler combustion chamber affects to type of nozzle
needed. Correct nozzle may differ from nozzle types suggested here.
After changing the nozzle - check the quantity of combustion air and the
position of the adjustment ring in the combustion head
4.3.
4.3.
Adjusting combustion air
Adjusting combustion air
Do a flue gas analyzis to verify adjustments