Burner operation
During burner operation, the control unit adjusts servomotors according to capacity
controller inputs. Servomotors adjust the gas regulator valve and air dampers between
partial load and full load according to the capacity demand.
Burner shutdown
If the current partial load exceeds the capacity demand, the burner shuts down and the
double solenoid valve closes.
PI diagram
Gas use, VGD valve, M series
Pos.
Item
Pos.
Item
1
Manual shut-off valve
12
Manual shut-off valve
2
Pressure switch, low
41
Air damper
42
Servomotor
43
Combustion air fan
44
Electric motor
3
Safety shut-off valves
3.1 Valve
3.2 Ac 3.4 (optional)
3.3 Actuator with pressure reg 3.4
3.4 Proof of closure switch (IRI: 2 pcs, when
capacity > 12.5 MBTU/h)
45
Differential pressure switch for air
4
Pressure switch (optional, when capacity < 12.5
MBTU/h)
51
Flame detector
5
Pressure switch, high
52
Ignition transformer
6
Manual shut-off valve
53
Burner hatch limit switch
7
Gas butterfly valve
54
Connection box
8
Servomotor
9
Manual shut-off valve
E
Air inlet
10
Pressure regulator
A
Gas inlet
11
Safety shut-off valve
B
Ignition gas inlet
82 (102)
M4263 2206EN