background image

     

WARNING:  If the information in these 

 

 instructions is not followed exactly, a fire

 

 or explosion may result, causing property

 

 damage, personal injury or death.

  Do not store or use gasoline or other 

 

 

 flammable vapors and liquids in the

 

 vicinity of this or any other appliance.

 WHAT TO DO IF YOU SMELL GAS:

  Do not try to light any appliance.
  Do not touch any electrical switch;
  do not use any phone in the building.

  

Immediately phone your gas supplier from 

  another building. Follow the gas supplierÕs
  instructions.

  

If you cannot reach your gas supplier call

  

the fire department.

Installation and service must be performed
by a qualified installer, service agency or
the gas supplier.

BURNER
MODEL

BILL OF MATÕL
NUMBER

DATE
CODE
WIRING 

  DIAGRAM

  FOR SERVICE CONTACT:

  name

  address

  phone

SAFETY  INFORMATION  TERMS. 

 The following terms are used to identify hazards, safety precautions or special notations

and have standard meanings throughout this manual.  They are printed in all capital letters using a bold typeface as shown below,
and preceded by the exclamation mark symbol:

DANGER

:

Identifies the most serious hazards which

 will

 result in severe personal injury or death.

WARNING: 

 Signifies hazards that 

could

 result in personal injury or death.

CAUTION: 

 Identifies unsafe practices which would result in minor personal injury or product and property damage.

ECONOMITE MODELS

400-33 AND F400-33

Gas Conversion Burners

In the United States, 

 Installation must conform with local 

codes

or, in the absence of local codes, with Installation of

 

the

National Fuel Gas Code, ANSI Z223.1-1992, 

or latest 

edition

available from American National Standard 

Institute. Further

reference should be made to 

the 

recommendation of your

fuel supplier.

In Canada

, Installation must conform with local codes or, in 

the

absence of local codes, with 

Installation Codes for 

Gas

Burning Appliances and Equipment, CGA 

Standard

CAN/CGA 1B-149.1 or 2

. When the conversion 

burner is used

on a Forced Air Central Furnace, the two 

yellow and black

warning labels in the literature envelope 

shall be attached in

accordance with 

Installation Code, 

CGA Standard CAN/CGA

1-B149, Clause 5.4.4.4.

 

Further reference should be made to

the recommendation 

of your fuel suppler.

WARNING: Additions, changes, conversions, and service

must be performed by an authorized MIDCO 

representative,

service agency, or the fuel supplier. 

Use only MIDCO

specified and approved parts.

INSTALLER:  Inform and demonstrate to the

user the correct operation and
maintenance 

of the gas utilization

equipment. Inform the 

user of the

hazards of storing flammable 

liquids and

vapors in the vicinity of this gas 

utilization

equipment and remove such 

hazards. Affix

this manual and associated 

literature

adjacent to the 

conversion 

burner. 

CODE COMPLIANCE IS THE SOLE
RESPONSIBILITY OF THE INSTALLER.

USER: Retain this manual for future reference.

If other than routine service or
maintenance as described in this manual and
associated literature is required, 

contact

a qualified service agency. DO NOT ATTEMPT
REPAIRS. An inadvertent service error could
result in a dangerous condition. 

INSTALLATION   AND 
SERVICE   INSTRUCTIONS

PRINTED IN U.S.A.

797

8449-84

¥

¥
¥

¥

¥

MIDCO

 

International Inc.

 

4140 WEST VICTORIA STREET ¥ CHICAGO, ILLINOIS 60646 ¥ (773) 604-8700 FAX: (773) 604-4070 ¥ http://www.midco-intl.com

Содержание ECONOMITE 400-33

Страница 1: ...Code ANSI Z223 1 1992 or latest edition available from American National Standard Institute Further reference should be made to the recommendation of your fuel supplier In Canada Installation must co...

Страница 2: ...ce area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner input When ventilating through hori zontal ducts grilles should be sized at not less t...

Страница 3: ...and flue collars Joints between sections of connector piping shall be fastened by sheet metal screws or other approved means The Vent Connector shall be supported for the design and weight of the mat...

Страница 4: ...during testing Exposing low pressure regulators and valves including manual valves to pressures over 1 2 PSIG 14 0 W C will cause damage and void all warranties When the gas supply line is about to be...

Страница 5: ...TION Do not exceed maximum or minimum rated capacity of burner model as shown in Table 1 Capacities shown are for a total pressure drop of 0 3 W C For 0 5 W C pressure drop multiply capacity shown by...

Страница 6: ...tronic flame detection circuit by turning off the pilot manual valve with pilot burning and Main Manual Shut Off Valve still closed The circuit to the main automatic pilot valve should be broken immed...

Страница 7: ...tion chamber pressure actu al air shutter setting and altitude extremes Do not subject the pilot to an inlet pressure over 14 0 W C See section VI PIPING for high pressure gas Note that the standard p...

Страница 8: ...low When the current is broken the valves close They will normally require no service However dirt or foreign matter on the valve seats could cause leakage If leakage is detected or if the operator ma...

Страница 9: ...TE sequence when it is powered The INITIATE sequence lasts for ten seconds unless the voltage or frequency tolerances are not met refer to Honeywell RM7895 literature for criteria When tolerances are...

Страница 10: ...HT FLAME SAFEGUARD REMAINS SET A Defective centrifugal actuator B Defective blower interlock switch C Slow motor D Defective purge timer E False flame signal F Defective flame safeguard 4 PILOT LIGHTS...

Отзывы: