background image

IV    CHIMNEY, VENT CONNECTOR AND

DRAFT CONTROL

WARNING:  The chimney shall be inspected for

unsafe conditions such as deteriorated masonry and
excessive soot or other blockage or potential block-
age. Installation must conform with local codes or in
the absence of local codes with NFPA , ANSI Z223.1
latest edition.

WARNING:  The vent connector shall not be con-

nected to a chimney already venting solid fuel burn-
ing  equipment, an incinerator or an open fireplace.

■  

The Vent Connector shall be made of non-

combustible, corrosion resistant material capable of with-
standing the vent gas temperature produced by the gas
utilization equipment and of sufficient thickness to with-
stand physical damage.

The Vent Connector shall be as short as possible.

The entire length shall be readily accessible for inspec-
tion, cleaning, and replacement.

The length of horizontal uninsulated Vent Connector

between chimney and a single gas utilization equipment
shall not exceed 75% of the the height of the chimney
above the connector, or 100% if the Vent Connector is
insulated.

The Vent Connector shall be installed so as to avoid

turns or other construction features which create exces-
sive resistance to flow of vent gas. It shall be installed
without any dips or sags and shall slope upward at least
1/4" per foot.

 A manually operated damper shall not be placed in

the Vent Connector or chimney of any gas utilization
equipment.

The Vent Connector shall be firmly attached to draft

hood outlets and flue collars. Joints between sections of 
connector piping shall be fastened by sheet-metal
screws or other approved means. The Vent Connector
shall be supported for the design and weight of the mate-
rial employed to maintain clearance and prevent physical
damage and separation of joints.

 

A draft hood or a barometric draft regulator shall be

installed in the same room or enclosure as the equip-
ment ins such a manner as to prevent any difference in
the pressure between the hood or regulator and the
combustion air supply (see Figures 3 and 4). In no case
shall the relief opening of the draft hood or barometric
draft regulator be located at a point lower than the top of
the highest flue passage in the equipment.

Gas utilization equipment requiring controlled draft

may be equipped with a listed double acting barometric
draft regulator, If approved by local codes (see Figure 4).

 A device which will automatically shut off gas to the

burner in the event of sustained backdraft is required. It
shall be of the listed manual reset type and installed and
adjusted by a qualified service technician in accordance
with the manufacturerÕs instructions.

Refer to gas utilization equipment manufacturer for

recommended vent connection requirements.

-3-

FIGURE 3     

Recommended Locations forDraft Hoods

FIGURE 1

Dry Base Boiler with Combustion Chamber

Liner (Warm Air Furnace Construction is Similar)

 Before permanently setting the burner in place, check

that the main burner casting and pilot ports are free of for-
eign materials, and also that the spark electrode assembly
has not been damaged or displaced.  See Figure 7.

FIGURE 2

Wet Base Boiler with Unlined 

Combustion Chamber

Содержание ECONOMITE 400-33

Страница 1: ...Code ANSI Z223 1 1992 or latest edition available from American National Standard Institute Further reference should be made to the recommendation of your fuel supplier In Canada Installation must co...

Страница 2: ...ce area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner input When ventilating through hori zontal ducts grilles should be sized at not less t...

Страница 3: ...and flue collars Joints between sections of connector piping shall be fastened by sheet metal screws or other approved means The Vent Connector shall be supported for the design and weight of the mat...

Страница 4: ...during testing Exposing low pressure regulators and valves including manual valves to pressures over 1 2 PSIG 14 0 W C will cause damage and void all warranties When the gas supply line is about to be...

Страница 5: ...TION Do not exceed maximum or minimum rated capacity of burner model as shown in Table 1 Capacities shown are for a total pressure drop of 0 3 W C For 0 5 W C pressure drop multiply capacity shown by...

Страница 6: ...tronic flame detection circuit by turning off the pilot manual valve with pilot burning and Main Manual Shut Off Valve still closed The circuit to the main automatic pilot valve should be broken immed...

Страница 7: ...tion chamber pressure actu al air shutter setting and altitude extremes Do not subject the pilot to an inlet pressure over 14 0 W C See section VI PIPING for high pressure gas Note that the standard p...

Страница 8: ...low When the current is broken the valves close They will normally require no service However dirt or foreign matter on the valve seats could cause leakage If leakage is detected or if the operator ma...

Страница 9: ...TE sequence when it is powered The INITIATE sequence lasts for ten seconds unless the voltage or frequency tolerances are not met refer to Honeywell RM7895 literature for criteria When tolerances are...

Страница 10: ...HT FLAME SAFEGUARD REMAINS SET A Defective centrifugal actuator B Defective blower interlock switch C Slow motor D Defective purge timer E False flame signal F Defective flame safeguard 4 PILOT LIGHTS...

Отзывы: