SPUD

 DRILL 

SIZE

#21(.159)

#15(.180)

#9(.196)
#3(.213)

#1(.228)

17/64(.265)

9/32(.281)

19/64(.296)

BURNER

INPUT

MBH

1

185
300

300
400

400
540

540

700

SPUD

DRILL

SIZE

11/32

(.343)

25/64

(.390)

7/16

3

 

(.437)

SPUD 

RE-

MOVED

 

DRIP

LEG

PILOT TUBING

MANUAL PILOT VALVE

PILOT REGULATOR

MAIN AIR

CONTROLLING SHUTTER

(COUNTER CLOCKWISE

TO OPEN)

BLOWER MOTOR

MAIN AND

REDUNDANT MAIN

GAS VALVES

BALL VALVE

TEST COCK

"PEEP" SIGHT

PILOT AND AIR TUBE

MAIN TEST TAP

PILOT TEST TAP

PRIMARY AIR ADJUSTMENT

SPARK GENERATOR

FLAME
SAFEGUARD
CONTROL

PILOT SOLENOID

MAIN

REGULATOR

MAIN REGULATOR

VENT

MANUAL

BALL VALVE

10

275
400
500
700
700

TYPE 

OF 

GAS

Natural 

Propane

Natural 

Propane

Natural

Propane

Natural

Propane

Natural

APPROXIMATE CAPACITY-MBH

LENGTH OF PIPE

100

225
300
475
450
700
700

PIPE

SIZE

3Ú4

(400-33 only)

1

1

Ú

4

1

 

1

Ú

2

2

20

300
350
550
700
700

40

200
250
375
500
700
700

60

200
300
400
625
600
700
700

-5-

FIGURE 5

Piping Connections

MANIFOLD

PRESSURE

W.C.

2

10.0"

MANIFOLD

PRESSURE

W.C.

2

1.5"
3.5"

2.0"
3.5"

2.0"
4.0"

1.85"

3.2"

NATURAL GAS

BURNER

INPUT

MBH

1

185

250

300
350
400

540

625

700

PROPANE GAS

CAUTION: Purge outside the building. Do not

purge into the gas utilization equipment combustion
chamber.

CAUTION:  Do not exceed maximum or minimum

rated capacity of burner model as shown in Table 1.

Capacities shown are for a total pressure drop of
0.3"W.C. For 0.5"W.C. pressure drop, multiply capacity
shown by 1.3 For higher permissible pressure drops,
consult your utility.

TABLE 2:

 Schedule 40 NPT Pipe-Capacity Chart

VII

MAIN GAS SPUD SELECTION

Burners are approved for use with NATURAL or
PROPANE gas and should be used only with the gas
specified on the rating plate.

■  

The gas input should be set at the heating rate

determined by the building heat loss and/or heating plant
survey, but not exceeding the rated maximum input of
the gas utilization equipment or Economite burner.

■  

Burners are shipped equipped for NATURAL gas; the

model 400 with a 11/32 drill spud installed, and the F400
with the spud removed.  Compare the gas input required
with the spud capacities shown in the spud table and, if
necessary, install the spare spud (see Figure 7).

DATA IS APPROXIMATE AND BASED ON Ò0"

OVERFIRE PRESSURE AT SEA LEVEL 

1.

Input range of spud. Adjust the main regulator to

vary the manifold gas pressure and burner input
within the range shown for a specific spud drill size.
With PROPANE, do not exceed 11.0"W.C. under
any circumstances.

2.

Approximate gas pressure at  manifold gas pressure

tap.

3.

Drill out 25Ú64 spare spud to 7Ú16.

TABLE 3

:  

Spud Capacity and Preliminary Gas Settings.

Содержание ECONOMITE 400-33

Страница 1: ...Code ANSI Z223 1 1992 or latest edition available from American National Standard Institute Further reference should be made to the recommendation of your fuel supplier In Canada Installation must co...

Страница 2: ...ce area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner input When ventilating through hori zontal ducts grilles should be sized at not less t...

Страница 3: ...and flue collars Joints between sections of connector piping shall be fastened by sheet metal screws or other approved means The Vent Connector shall be supported for the design and weight of the mat...

Страница 4: ...during testing Exposing low pressure regulators and valves including manual valves to pressures over 1 2 PSIG 14 0 W C will cause damage and void all warranties When the gas supply line is about to be...

Страница 5: ...TION Do not exceed maximum or minimum rated capacity of burner model as shown in Table 1 Capacities shown are for a total pressure drop of 0 3 W C For 0 5 W C pressure drop multiply capacity shown by...

Страница 6: ...tronic flame detection circuit by turning off the pilot manual valve with pilot burning and Main Manual Shut Off Valve still closed The circuit to the main automatic pilot valve should be broken immed...

Страница 7: ...tion chamber pressure actu al air shutter setting and altitude extremes Do not subject the pilot to an inlet pressure over 14 0 W C See section VI PIPING for high pressure gas Note that the standard p...

Страница 8: ...low When the current is broken the valves close They will normally require no service However dirt or foreign matter on the valve seats could cause leakage If leakage is detected or if the operator ma...

Страница 9: ...TE sequence when it is powered The INITIATE sequence lasts for ten seconds unless the voltage or frequency tolerances are not met refer to Honeywell RM7895 literature for criteria When tolerances are...

Страница 10: ...HT FLAME SAFEGUARD REMAINS SET A Defective centrifugal actuator B Defective blower interlock switch C Slow motor D Defective purge timer E False flame signal F Defective flame safeguard 4 PILOT LIGHTS...

Отзывы: